CYZRS-20A Three Channel DC Resistance Rapid Tester

NegotiableUpdate on 01/22
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Product Overview Implementation Standard: DL/T845.3-2004CYZRS-20A Three Channel DC Resistance Rapid Tester (hereinafter referred to as DC Resistance Tester) is a generation product for measuring transformer DC resistance. It is optimized and designed by Chuangyi Electric for measuring the DC resistance of large capacity transformer three-phase windings

Product Details

Product Overview


  • Execution standard: DL/T845.3-2004
  • The CYZRS-20A Three Channel DC Resistance Rapid Tester (hereinafter referred to as the DC Resistance Tester) is a generation product for measuring the DC resistance of transformers. It is optimized and designed by Chuangyi Electric for measuring the DC resistance of three-phase windings of large capacity transformers. Simultaneously test the DC resistance of the three-phase winding of the transformer. For on load tap changers, there is no need for discharge, and the tap changer can be directly adjusted. The measurement time is one-third of traditional single-phase measurement, which can greatly shorten the working time and labor intensity. The direct resistance meter adopts a large screen LCD display with a fully Chinese graphical interface, which is clear and intuitive, and the operation is very simple. And equipped with a panel printer and large capacity non-volatile memory, it can conveniently store and print measurement results. The test data is stable, fast, and has good repeatability, making it suitable for on-site measurement of transformer DC resistance.
  • For on load tap changers, there is no need to discharge and the tap can be directly adjusted, which can greatly shorten the working time. It adopts a large screen LCD display with a fully Chinese graphical interface, which is clear and intuitive, and easy to operate. The test data is stable, fast, and has good repeatability. It is equipped with a panel printer and a large capacity non-volatile storage for on-site measurement of transformer DC resistance, which can conveniently store and print measurement results


Product Parameters

test current single-phase 1 A 5A 10A 20A 40A
three-phase 1 A 5A 10A 20A
measurement range single-phase 1 A 10mΩ~20 Ω
5A 1mΩ~4Ω
10A 1 mΩ~2 Ω
20A 1mΩ~1Ω
40A 1 mΩ~0.5Ω
three-phase 1 A 10mΩ~6 Ω (每相)
5 A 1mΩ~1 Ω(每相)
10A 1 mΩ~0.6Ω (每相)
20A 1mΩ~0.3Ω(每相)
measurement accuracy ± 0.2% (full range)
resolution 0.1μ Omega
Data storage capacity 150 sets
power supply AC 220V±22V,50Hz±2 Hz
working environment Environmental temperature: 0 ° C to 40 ° C
Relative humidity: ≤ 80%