fan impeller

NegotiableUpdate on 03/20
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
Product Details
Product NameFire Control Valve Series
Details:
structure
Main components: valve body, valve blades, shaft, bushing, actuator
Rectangular valve body thickness: L=210, 260
There are three types of flange widths: 30, 40, and 50. The conventional width is 30. Please specify when designing or ordering
When the W size is greater than 1250, add a middle frame and separate the blades.
Valve body area ≥ 1m2, with 2 actuators installed.
Main surgical parameters
Fuse operating temperature: 70 ℃ (or 280 ℃)
Valve fire resistance rating: 1.5h
Leakage rate<pressure difference 300pa>; ≤700m3 /m2 .h
Fully open resistance coefficient:<0.5

Product Name: Air volume control valve
Details:
air volume regulating valveIt is an air conditioning terminal accessory in the ventilation, air conditioning, and air purification engineering of industrial plants and civil buildings. It is generally used in air conditioning and ventilation system ducts to adjust the air volume of branch pipes, and can also be used for mixed regulation of fresh and return air
Product NameMulti leaf smoke exhaust outlet
Details:
positive pressure air supply outlet
Function: When a fire occurs, the internal motor will open the air vent, the temperature and smoke sensing or manual fire alarm will be activated, the positive pressure fan at the top of the tower will automatically open, and the supply shaft will be pressurized for air supply. The front room of the staircase will pass throughpositive pressure air supply outletIt will continuously supply air to the front room to maintain positive pressure, ensuring that smoke does not spread in this area and providing space for people to escape. When the temperature exceeds 280 ° C, there is no possibility for people to escape. The internal fuse will melt, and the air vent will automatically close to prevent the spread of fire.
Application: According to the National Code for Fire Protection and Smoke Exhaust Design of High rise Buildings, independent mechanical smoke exhaust systems should be installed in the following areas
1: Smoke proof staircases, fire elevator lobbies, or shared lobbies that do not have natural smoke exhaust conditions.
2: The smoke proof staircase with natural smoke exhaust does not have a front room with natural smoke exhaust.
3: A closed refuge layer.
In the above three situations, a mechanical pressurized air supply system is virtually installed. Its end ispositive pressure air supply outletBelow are the styles of the product and drawings
Product NamePlate type smoke exhaust outlet
Details:
Scope of use:
The smoke exhaust outlet of the smoke exhaust system installed in corridors or smoke proof front rooms, as well as windowless rooms, can be suspended from the ceiling or installed on the side wall.
Features
1. Normally closed, with a DC24V electrical signal from the control center, the smoke exhaust vent quickly opens.
2. Remote manual opening.
3. Remote manual reset.
4. Output the activation signal and interlock the relevant equipment.
5. The plate type exhaust outlet has the function of closing again when the flue gas temperature reaches 280 degrees after opening.
Production of fire dampers and smoke exhaust dampers:
1. In case of fire, the frame (shell) and blades should be able to prevent deformation and failure, and the thickness of their plates should not be less than 2mm.
2. Fusible parts should be standard products recognized by the door, and their melting point temperature should comply with the design specifications.
3. The valve action should be reliable, and it should be tight when closed. Its allowable air leakage should comply with relevant regulations.
Product NameFire damper, smoke exhaust valve regulating valve
Details:
Fire damper, smoke exhaust valve regulating valve
structure
Main components: valve body, valve blades, shaft, bushing, actuator
Rectangular valve body thickness: L=210, 260
There are three types of flange widths: 30, 40, and 50. The conventional width is 30, and the design or
Please specify when placing an order
When the W size is greater than 1250, add a middle frame and separate the blades.
Valve body area ≥ 1m2, with 2 actuators installed.
FSD (G), FSD (F) simple fire damper fire control valve Main surgical parameters
Fuse operating temperature: 70 ℃ (or 280 ℃)
Valve fire resistance rating: 1.5h
Leakage rate<pressure difference 300pa>; ≤700m3/m2.h
Fully open resistance system:<0.5
structure
Main components: valve body, valve blades, shaft, bushing, actuator
Circular valve body thickness: When ¢ ≤ 320, L=D; When ¢>320
When using Fangjieyuan, L=320
When the W size is greater than 1250, add a middle frame and separate the blades.
When the flange width ¢ ≤ 320 is 25, when ¢ ≤ 500 is 30, and when ¢ ≤ 560
At 40 hours Circular fire control valve
Valve body area ≥ 1m2, with 2 actuators installed.
Main surgical parameters
Fuse operating temperature: 70 ℃ (or 280 ℃)
Valve fire resistance rating: 1.5h
Leakage rate<pressure difference 300pa>; ≤700m3/m2.h
Fully open resistance system:<0.5
structure
Main components: valve body, valve blade, shaft, bushing, fuse
actuator
Rectangular valve body thickness: L=210, 260
There are three types of flange widths: 30, 40, and 50. The conventional width is 30, and the design or
Please specify when placing an order
When the W size is greater than 1250, add a middle frame and separate the blades.
Valve body area ≥ 1m2, with 2 actuators installed.
Main surgical parameters
Leakage rate<pressure difference 300pa>; ≤700m3/m2.h
PSD (ZD) fully automatic smoke and fire damper Valve fire resistance rating: 1.5h
Fuse operating temperature: 70 ℃ (or 280 ℃)
Control voltage: DC24V
Operating current: 0.2A
Reset current: 0.3A
Action time: Shunjian
Reset time: ≤ 12 seconds
Fully open resistance coefficient:<0.5
structure
Main components: valve body, valve blade, shaft, bushing, fuse
actuator
Rectangular valve body thickness: L=210, 260
There are three types of flange widths: 30, 40, and 50. The conventional width is 30, and the design or
Please specify when placing an order
When the W size is greater than 1250, add a middle frame and separate the blades.
Valve body area ≥ 1m2, with 2 actuators installed.
The torque of the actuator's bull spring can be adjusted in three levels FFYH (J) (JF) smoke and fire damper
Main surgical parameters
Fuse operating temperature: 70 ℃
Valve fire resistance rating: 1.5h
Leakage rate<pressure difference 300pa>; ≤700m3/m2.h
Control voltage: DC24V
Operating current: 0.2A
Micro switch contact capacity: AC 380V 3A
Fully open resistance coefficient:<0.5
Smoke exhaust and fire damper series
PYK-DY panel exhaust outlet
Performance: Main technical parameters:
1. Smoke sensing electrical signal or electrical signal instruction to open the smoke exhaust port for smoke exhaust, Leakage rate (pressure difference 300Pa) ≤ 700m3/m2. h
2. Use the button of the remote actuator to open the exhaust port for smoke exhaust Control voltage: DC24V
3. After the smoke exhaust outlet is opened, an electrical signal will be output to alarm or activate the interlock wind Micro switch contact capacity: AC 380V 3A
Machine. Resistance<0.5 when the air vent is fully open
After PYK-DYW is turned on, if the air temperature rises to 280 ℃
Automatically close under the action of temperature fuse.
5. Can be manually reset from a distance.