Welcome Customer !

Membership

Help

Shanghai Taixi Electric Co., Ltd
Custom manufacturer

Main Products:

mechb2b>Products

Shanghai Taixi Electric Co., Ltd

  • E-mail

    service@taixiele.com

  • Phone

    13356192265

  • Address

    Shangzhai Industrial Zone, Liushi Town, Yueqing City, Zhejiang Province

Contact Now

TXL7-63 miniature circuit breaker (10KA breaking capacity)

NegotiableUpdate on 07/09
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

1、 Scope of application

Product Details

1、 Scope of application

TXL7-63High score cutoffminiature circuit breakerMueller circuit breakerL7 circuit breaker10KA miniature circuit breaker with breaking capacity)It is mainly used for protection distribution lines with AC 50Hz/60Hz, rated working voltage up to 400V (380V), rated current up to 63A, and rated short-circuit breaking force not exceeding 10KA. It is used for infrequent connection, disconnection, and conversion of the line, and has overload and short-circuit protection functions. At the same time, it has powerful auxiliary function modules, such as auxiliary contacts, alarm indicator contacts, shunt release, remote release control of undervoltage release, and other modules.
Circuit breakerCompliant with GB10963.1 and IEC60898-1 standards.

2、 Model and its meaning

PRODUCT MODEL number of poles Release type Rated current
TXL7-63 1P C 63

1P
2P
3P
4P
B: Type B
C: Type C
D: D-type
1:1A 10:10A 32:32A
2:2A 16:16A 40:40A
3:3A 20:20A 50:50A
4:4A 25:25A 63:63A
6:6A

3、 Normal working and installation conditions

The upper limit of the surrounding air temperature shall not exceed+40 ° C, the lower limit shall not be lower than -5 ° C, and the average temperature over 24 hours shall not exceed+35 ° C.
The altitude of the installation location should not exceed 2000m.
The relative humidity of the atmosphere should not exceed 50% when the ambient air temperature is+40 ° C. Higher relative humidity is allowed at lower temperatures. Special measures should be taken for condensation that occasionally occurs on the surface of the product due to temperature changes.
Pollution level: Level II.
Installation conditions: Installed in a location without significant impact or vibration, and in a medium without explosive hazards.
Installation method: TH35-7.5 installation rail is used for installation.
Installation category: Level II and III.

4、 Product classification

Circuit breakers are classified according to the number of poles, including single pole, two pole, three pole, four pole, and other types;
Circuit breakers are classified according to the instantaneous tripping current form: C type, D type (B type can be customized if required);
The rated current of circuit breakers includes: 1A, 2A, 3A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;
The rated voltage of the circuit breaker is 230V (220V)/400V (380V) (230V for single pole, 400V for two pole, three pole, and four pole);

5、 Description of Release Types

Type B: Suitable for providing line protection for resistive loads and low inductance distribution systems, as well as line protection for many electronic circuits, commonly used for electric vehicle protection.
Type C: Suitable for providing line protection for inductive loads and high sensitivity lighting systems, generally referred to as distribution protection.
D-type: Suitable for providing line protection to distribution systems with high inductive loads and large impact currents, generally referred to as power protection.

6、 Polar number explanation

TXL7-63 miniature circuit breaker (L7) divided by pole number:
A. Single pole circuit breaker;
B. A two pole circuit breaker with two protective poles;
C. A three pole circuit breaker with three protective poles;
D. A four pole circuit breaker with four protective poles.

7、 Technical parameters

TXL7-63 miniature circuit breakerRated short-circuit capacity

Rated current number of poles Rated voltage (V) Rated short-circuit current (A)
1~63A 1P 230/400 10000
1~63A 2P、3P、4P 400 10000

TXL7-63Mechanical and electrical lifespan

category number of times Operation frequency (times/hour) Rated current (A)
Electrical life 10000 240 6~32
120 40~63
mechanical life 10000 240 6~63

Overcurrent protection characteristics under ambient temperature of 30 ℃~35 ℃

Serial Number Rated current of release device (A) Initial state test current appointed time Expected results notes
1 6~63 cold state 1.13In t≤1h Do not release
2 6~63
1.45In t≤1h trip The current remains stable within 5 seconds
Rise to the specified value
3 In≤32 cold state 2.55In 1s<t<60s trip
In>32 cold state 2.55In 1s<t<120s trip
4 6~63 cold state 5In t≤0.1s Do not release C Type
10In t<0.1s trip
10In t≤0.1s Do not release D-type
20In t<0.1s trip
Release type Rated current A Rated short-circuit breaking capacity A COSΦ
C、D 6≤In≤63 10000 0.45~0.50

8、 Appearance and installation dimensions