TXDB1L-63 residual current circuit breaker

NegotiableUpdate on 07/09
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

1、 Scope of application

Product Details

1、 Scope of application

TXDB1L-63causeDZ30LEImproved, the internal circuit board is composed of integrated circuits, with superior and more reliable performance! TXDB1L-63 (DPN Vigi) (phase line+neutral line+leakage+overvoltage) protection circuit breaker(Anti leakage protection switchSingle-phase residual current switch)Suitable for single-phase residential power lines with AC frequency of 50Hz/60Hz, rated voltage of 230V, and rated current up to 63A. It is used for leakage protection and can also protect against overload and short circuit of civil electrical lines. It can also frequently turn on and off electrical devices and lighting lines under normal conditions, especially suitable for industrial and commercial lighting distribution systems. shouldLeakage circuit breakerHaving a small volume and high breaking ability; Zero and live wires are cut off simultaneously, and protection against leakage can still be provided even when the live wires are reversed.
The filtering device inside the electronic leakage overvoltage protection circuit breaker can prevent false tripping caused by instantaneous voltage (interference from lighting and other equipment lines) and instantaneous current (such as high-capacity load lines).

Circuit breakerCompliant with standards such as GB16917.1.

2、 Model and its meaning

3、 Normal working and installation conditions

The ambient air temperature is -5 ℃~+40 ℃, and the daily average temperature does not exceed+35 ℃.
The altitude shall not exceed 2000m.
The relative humidity of the air should not exceed 50% at a maximum temperature of+40 ℃, and higher humidity is allowed at lower temperatures, such as reaching 90% at+20 ℃. However, appropriate measures should be taken for occasional condensation that may occur due to temperature changes.
The pollution level is level 2.
The electromagnetic environment is environment B.
The external magnetic field of the installation site should not exceed 5 times the geomagnetic field in any direction.
■ Installed using standard mounting rails (TH35-7.5 type), installed in distribution boxes, cabinets or boxes.
During installation, it is generally installed vertically, with an inclination of no more than ± 5 ° between the installation plane and the vertical plane, and the handle facing upwards as the power on position.
The installation site should be free from significant impact, vibration, hazardous (explosive) media, and rain and snow invasion.
Installation category: Level II, Level III.

4、 Main technical parameters

Rated current: 6, 10, 16, 20, 25, 32, 40, 50, 63A
Rated working voltage: 230/400V AC
Rated insulation voltage: 500V
Rated residual operating current: 30mA
■ Breaking capacity: 4.5kA
■ Trip indication: There is a residual current action trip indication window on TXDB1L. When the leakage fault trips, the window changes from colorless to red
Mechanical lifespan: 8000 cycles
Electrical lifespan: 2000 cycles
■ Wiring: 6~63A, can connect wires of 25mm ² and below
Compliant with standard: IEC61009-1/GB16917.1
■ Compliant with certifications: CCC, Cb certification
■ Tripping characteristics: C-shaped curve, protecting conventional loads and distribution cables, instantaneous tripping range (5-10) In

Current level (A) screw Rated torque (N.m) Ultimate torque (N.m) Standard torque (N.m)
6~40 M5 2.5 45 2.0

Main technical parameters

model number of poles Rated current (A) Rated short-circuit breaking capacity Type of release device
Voltage (V) Short circuit breaking capacity (A) cosφ
TXDB1L-63 1P+N 6. 10, 16, 20, 25
32, 40, 50, 63
230 4500 0.65~0.7 C

Rated residual operating current: 30mA;
Rated residual non operating current: 15mA;
Rated residual connection and disconnection capacity: 2000A;
Leakage action time: ≤ 0.1s;
Withstand impulse voltage: Uimp=4kV;
Delay action characteristics: (see Table 2)

Release type Rated current (A) Test current (A) Initial state appointed time Agreed time expected results
C ≤63 1.13In cold state t≤1h Do not release
≤63 1.45In Hot state t<1h trip
≤32 2.55In cold state 1s<><>< td=''> <><><60s<> trip
>32 1s<><>< td=''> <><><120s<>

Instantaneous action characteristic

Type of release device Test current (A) Initial state appointed time Expected results
C 5In cold state t≤0.1s Do not release
C 10In cold state t<0.1s trip

5、 Institution and working principle

TXDB1L-63 residual current circuit breaker is a current operated electronic residual current circuit breaker. It is an integrated small residual current protection circuit breaker designed specifically for single-phase circuits, with the characteristics of large capacity and small volume, saving resources and space for users to install.
The circuit breaker is mainly composed of contacts, housing, operating mechanism, electromagnetic system, trip mechanism, arc extinguishing device, zero sequence transformer, electronic discrimination control circuit, trip indication and other parts, with overload, short circuit and leakage protection functions.
Working principle of residual current circuit breaker
Overload protection: When the circuit is overloaded, the bimetallic strip pushes the lock buckle, causing the circuit breaker to trip and provide action protection;
Short circuit protection: When a short circuit fault occurs in the circuit, the electromagnetic coil generates a strong magnetic field, and the iron core quickly pushes the lock buckle, causing the circuit breaker to trip (cutting off the power supply within 0.1 seconds) and providing action protection;
Leakage protection: When a leakage fault occurs in the protected circuit, the current vector sum of the zero sequence current transformer is not equal to zero, and the secondary output terminal of the transformer generates voltage, causing the thyristor to conduct and the electromagnetic trip system to act, causing the trip link to push the circuit breaker to trip and cut off the power supply within 0.1 seconds, thus playing a leakage protection role.

6、 Appearance and installation dimensions

7、 Wiring diagram