TXB8F-125 electric meter external automatic reclosing

NegotiableUpdate on 07/09
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

1、 Scope of application

Product Details

1、 Scope of application

TXB8F-125External automatic reclosing of electric meterminiature circuit breaker(also known asElectric meter air switch)(hereinafter referred to asCircuit breaker)Suitable for AC 50Hz, rated working voltage up to 400V, and rated working current up to 125A lines, it can perform remote automatic closing and opening control or automatic signal control closing and opening of the line, while also providing overload and short circuit protection for the line. It can also be equipped with a voltage loss release device to achieve the function of power-off opening and automatic closing when powered on. At present, it is widely used in photovoltaic grid connected AC distribution boxes, as well as in situations where personnel are difficult to access, maintenance personnel cannot be in place in a timely manner, unmanned situations, and situations with high requirements for power supply continuity. TXB8F-125 prepaid electric meter automatic reclosing small circuit breaker is a new type independently developed by Taixi Electric, which can reliably and automatically disconnect and cut off power due to arrears through a motor, and automatically close and continue power after payment. It can also effectively protect the line and terminal equipment, and provide feedback on the closing and opening status signals.
Automatic reclosing circuit breakerCompliant with standards: GB10963.1, IEC60898-1, with international advanced level.

2、 Model and its meaning

PRODUCT MODEL number of poles Release type Rated current of trip type
TXB8F-125 1P+N C 125

1P+N
3P+N
C: Type C

6:6A 20:20A 50:50A

10:10A 32:32A 63:63A

16:16A 40:40A 80:80A

100:100A 125:125A

3、 Structural characteristics

TXB8F-125 seriesAutomatic reclosing circuit breakerAssembled from 1P+N or 3P+N high segmented miniature circuit breakers and 18mm wide standard 1P intelligent trip reclosing modules.
The external small circuit breaker of the electric meter needs to receive remote control signals (such as energy meter control signals, etc.) to achieve remote reclosing function;
All poles are equipped with overcurrent protection and short-circuit protection functions;
The maximum rated breaking capacity can reach 10KA;
The external circuit breaker of the electricity meter is equipped with two working modes: "automatic" and "manual", and has an LED indicator light (lit to indicate normal charging status)
The front side of the external circuit breaker of the electric meter is equipped with standard interfaces for closing signal (C) and feedback signal (F);
The external miniature circuit breaker of this meter does not support remote closing function in "manual mode" (similar to the prepaid dedicated circuit breaker function of an energy meter)
The external miniature circuit breaker of the electric meter cannot be manually closed in any state after receiving a disconnection command, and the internal contacts are always in the disconnected position when closed.
The reclosing circuit breaker has a memory function, and when the power is cut off and the power is restored, the product will always maintain its working state during the power outage;
The remote automatic closing time of the reclosing circuit breaker is less than 2 seconds;
The static power consumption of the intelligent trip reclosing module of the automatic reclosing circuit breaker is less than 0.2mA;
When the air switch of the electric meter is in the "user arrears" state, the internal contacts always handle the disconnected position, and manual closing will not be possible;
The air switch of the electric meter adopts an internal shaft synchronous transmission method to achieve automatic closing function;
The operating mechanism of the circuit breaker is a free release mechanism with energy storage, which enables quick contact closure and quick disconnection, overcoming the adverse effects of the speed of the handle during the automatic closing and opening process of the circuit breaker, greatly improving the service life of the product; During normal operation, the contact can only remain in the closed or open position;
Automatic reclosing and disconnecting devices, consisting of controllable silicon, integrated chips, motors, and gears as driving components;
The shell and components are made of high flame retardant, high temperature resistant, and impact resistant plastic.
The air switch of the electric meter complies with the latest technical specifications of the State Grid Corporation of China in 2015

4、 Normal working conditions and installation conditions

Environmental temperature: -25 ℃~+60 ℃;
Altitude: The altitude of the installation site shall not exceed 2000m;
Installation category: Level II and III;
Installation method: TH35-7.5 steel installation rail is used for installation.

5、 Main parameters and technical performance

Divided by rated current ln: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A.
POLE: 1P+N single-phase, 3P+N three-phase.
According to the form of instantaneous release of circuit breakers: C-type (5ln~10ln).
Electrical lifespan: 4000 cycles, cos=0.85~0.9。
Mechanical lifespan: 20000 cycles.
Protection level: IP20.
Rated working voltage Ue: 1P+N/2P 230V AC/50Hz; 3P+N/4P 400V AC/50Hz。
Energy level: 3
Remote automatic closing time:<2s
Power on delay: ≥ 4s
Control level current: ≤ 1mA
Leakage current of phase line: < 0.2mA
Rated impulse withstand voltage: 6KV
Rated short-circuit breaking capacity: 10000A (6~80A); 6000A(100~125A)
Connecting external signal control wires: The wire has a cross-sectional area of 0.6mm ² and a length of 30cm (other lengths can be specially produced) with crimped terminal blocks.
Terminal block: Suitable for connecting wires below 35mm. The wiring method is to tighten the wires with screws and apply a torque of 3.5Nm.

Rated current range In (A) Maximum power consumption per pole (W)
32<In≤40 6.5
40<In≤50 8
50<In≤63 11.5
63<In≤80 13.5
80<In≤125 15

Overcurrent protection characteristic, at 30 ℃~35 ℃

Serial Number Rated current test current Initial state Set time Expected results notes
1 6~125 1.13In cold state t≥1h ln≤125A
t≥2h ln>125A
Do not release
2 6~125 1.45In Immediately following the previous item
After the experiment, proceed
t<1h ln≤125A
t<2h ln>125A
trip The current remains stable within 5 seconds
Rise to the specified value
3 ln≤32 2.55In cold state 1s<><>< td=''><><> trip
ln>32 2.55In cold state 1s<><>< td=''><><> Do not release Through closed assistance
Switch on current
4 6~125 5In
10In
cold state t≤0.1s
t<0.1s

Do not release

trip

Automatic reclosing and opening characteristics

model rated control voltage Automatic closing time Automatic opening time Repetitive operation time interval
TXB8-125 230V t<10s t<10s 3min

The term 'cold state' refers to the absence of load before testing at the reference calibration temperature.

Serial Number phase line Control model line Initial state Post action state notes
1 AC 220V opening Close (Jumping from 0V to AC220V) Received closing signal
2 AC 220V AC 220V Close opening Manual disconnection
3 AC 220V AC 220V opening Close Manual closing
4 AC 220V Close opening (Jumping from AC220V to 0V) Received opening signal
5 AC 220V opening opening (Jumping from AC220V to 0V) Received opening signal
6 AC 220V 0V opening opening 0V control signal, no closing allowed (manual)
7 AC220V→
0V→AC220V
AC 220V Close Close Handle the closing status before the power outage of the line, and then switch it back on after the power outage
Electricity, it is not allowed to open and then close the circuit
8 AC220V→
0V→AC220V
AC 220V opening opening Process the circuit breaker status before power outage, and then switch it back on after power outage
Electricity, do not allow closing or opening after closing
9 0V / opening opening Power off the circuit and maintain the original state
10 0V / Close Close Power off the circuit and maintain the original state

Correction values for current used at different ambient temperatures

Temperature (℃)

Correct current value (A)

Rated current (A)

-30 -20 -10 0 10 20 30 40 50 60
10 12.5 12.4 11.9 11.3 10.8 10.4 10 9.7 9.2 8.5
16 20 19.8 18.9 18.1 17.3 16.5 16 15.5 14.6 13.8
20 25 24.8 23.6 22.6 21.1 20.6 20 19.4 18.2 17.2
25 21.25 31 29.5 28.3 27 25.8 25 24.3 22.8 21.3
32 40 39.7 37.8 36.2 34.6 33 32 31 28.8 27.2
40 50 49.6 47.2 45.2 43.2 40.8 40 38.4 37.2 .5.2
50 63.5 62.5 59 56.5 54 51.5 50 48 45.5 43
63 80.01 78.8 74.3 71.2 68 64.9 63 60.5 57.3 54.2
80 101.6 100 94.3 90.4 82.4 82.4 80 76.8 72.8 68.8
100 122.8 122 118.3 112.6 108.7 103.4 100 95.8 90.1 81.8
125 148.8 144 140.2 134.8 130.4 128.9 125 118.9 111.8 108.5

6、 Trip characteristic curve of external circuit breaker for electric meter

Overload current trip characteristic curve of automatic reclosing circuit breaker

C-type release characteristic curve

7Electric meter air switchWiring requirements

Suitable for wire connections of 36mm ² and below, the wiring method is to use screws to tighten the wiring, with a torque of 3.5N · m.

Rated current In (A) Nominal cross-sectional area of copper wire (mm ²)
1~6 1
10 1.5
16~20 2.5
25 4
32 6
40~50 10
63 16
80 25

8Electric meter air switchApplication examples

9Electric meter air switchAppearance and installation dimensions