Si792 security explosive transmitter

NegotiableUpdate on 01/22
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Si792 security explosion-proof transmitter, two-wire intrinsic safety explosion-proof transmitter, can be connected to Hach GLI sensor: $r $n ● pH differential or composite pH/ORP sensor $r $n ● GLI 3400 series inductive conductivity sensor $r $n ● GLI 3700 series non-polar conductivity sensor (concentration analyzer)

Product Details

The two-wire intrinsically safe explosion-proof transmitter can be connected to the Hach GLI sensor
● pH differential or composite pH/ORP sensor
GLI 3400 series inductive conductivity sensor
GLI 3700 series non-polar conductivity sensor (concentration analyzer)

Multiple communication protocols
The Si792 transmitter has digital communication function, which can easily connect to the selected communication network, including HART? 、 PROFIBUS PA、 Or Foundation? Optional protocols such as Fieldbus.

Application of different explosion-proof levels
Class I, Division 2 (C I, D 2), only equipped with HART protocol;
● Class I, Division 1 (C I, D 1), intrinsically safe, equipped with HART,
PROFIBUS PA or Foundation Fieldbus protocol. Certified by FM, CSA, and ATEX professional organizations.

Sensor self diagnosis
The Si792 transmitter can perform self diagnosis and sensor monitoring, such as monitoring potential asymmetry, electrode slope, response time, cable status, glass electrode status information, etc.





The sensor is in good condition.
The sensor condition is average and needs to be replaced as soon as possible.
Zero and slope values cannot guarantee correct calibration or
Sensor malfunction or breakage.

By setting, different password protections can be set:
● Sensor calibration
● Transmitter settings
● Administrator function

Measurement range: pH: -2.00~16.00 ORP: -1500~1500 mV Conductivity: 0~1000 mS/cm Acid base concentration: 0~100% Temperature: -20.0~150.0 ° C for PT 100, PT 1000; -20.0-110.0 ° C for NTC 300 ohms signal output: 4-20 mA analog/digital output operating temperature: -20~55 ° C storage temperature: -20~70 ° C relative humidity: 10~80%, non condensing industrial certification: EN 61326 protection level: IP 65 cable joint: 3 holes that need to be penetrated, used for installing cable joint M20x1.5 installation method: wall mounted, panel or clamp type (horizontal or vertical) chassis size: 144 x 144 x 105 mm controller weight: about 1 kg shell material: PBT polyester resin