E-mail
1815108006@qq.com
-
Phone
13855073989
-
Address
No. 20 Renhe South Road, Tianchang City, Anhui Province
Anhui Tiankang (Group) Co., Ltd. Marketing Center
1815108006@qq.com
13855073989
No. 20 Renhe South Road, Tianchang City, Anhui Province
SWP-LCD-NDR805 monochrome self-tuning control recorder
SWP-LCD-NDR805 small monochrome self-tuning control recorderProduct Introduction
SWP-LCD-NDR805 small monochrome self-tuning control recorderThe table is suitable for systems that require high-precision measurement control.
SWP-LCD-NDR805 small monochrome self-tuning control recorderIntegrated with analog instruments, it can digitally display and control measurement signals such as temperature, pressure, liquid level, and speed, making the display of measurement values clearer and more intuitive.
1It can be equipped with one PID control output and one transmission output respectively, and is suitable for various measurement and control scenarios.
2Manual/automatic undisturbed switching, parameters can be modified in manual mode.
3It has multiple adjustable output modes (PWM output, controllable trigger output, solid-state relay output, and voltage/current output).
SWP-LCD-NDR805 small monochrome self-tuning control recorderProduct Parameters
model |
code |
Instructions |
||||||||||
SWP -LCD-N |
□□□-□□□-□□-□□-□-□ |
New generation PID self-tuning controller |
||||||||||
appearance characteristics |
D S DR SR |
Horizontal display instrument Vertical display instrument Horizontal display instrument with recording function Vertical display instrument with recording function |
||||||||||
Overall dimensions |
8 |
160×80mm(Horizontal) 80×160mm(Vertical) |
||||||||||
control function |
05 |
|
|
|
|
|
|
|
PIDSelf-tuning control |
|||
contact method |
0 2 4 8 9 |
|
|
|
|
|
|
No communication The communication interface is RS-232C The communication interface is RS-422 The communication interface is RS-485 Special specifications for communication interfaces |
||||
controlled output |
□ |
|
|
|
|
|
Refer to 'Control Output Mode' |
|||||
transmitter output |
□ |
|
|
|
|
Refer to 'Transmission Output Method' |
||||||
input type |
□□ |
|
|
|
Refer to 'Input Types' |
|||||||
*Alarm method |
N H L |
|
|
No alarm (can be omitted) upper limit alarm Lower limit alarm |
||||||||
Second alarm method |
□ |
|
Refer to 'Alarm Output Method' |
|||||||||
Feed output |
P |
DC24VFeed output |
||||||||||
power supply method |
W T |
DC24Vpower supply AC90~265V power supply (switch mode power supply) AC220VPower supply (linear power supply, can be omitted) |
||||||||||
input type
code |
input type |
measurement range |
code |
input type |
measurement range |
code |
input type |
measurement range |
01 |
B |
400~1800℃ |
09 |
Pt100.1 |
-99.9~199.9℃ |
17 |
30~ 350Ω |
-1999~99999 d |
02 |
S |
0~1600℃ |
10 |
Cu50 |
-50.0~150.0℃ |
18 |
Special specifications |
User specific |
03 |
K |
0~1300℃ |
11 |
Cu100 |
-50.0~150.0℃ |
19 |
4~20mA square root |
-1999~99999 d |
04 |
E |
0~1000℃ |
12 |
4~20mA |
-1999~99999 d |
20 |
0~10mA square meter |
-1999~99999 d |
05 |
T |
-199.9~320.0℃ |
13 |
0~10mA |
-1999~99999 d |
21 |
1~5 V square root |
-1999~99999 d |
06 |
J |
0~1200℃ |
14 |
1~5V |
-1999~99999 d |
22 |
0~5 V square root |
-1999~99999 d |
07 |
Wre3~25 |
0~2300℃ |
15 |
0~5V |
-1999~99999 d |
23 |
Fully switchable input |
Please refer to the table below for details |
08 |
Pt100 |
-200~650℃ |
16 |
0~20mA |
-1999~99999 d |
To fully switch inputs, simply set the secondary parameters of the instrument to switch between multiple division marks. The division marks that can be input are as follows
code |
input type |
code |
input type |
code |
input type |
code |
input type |
code |
input type |
01 |
B |
05 |
T |
09 |
Pt100.1 |
14 |
1~5 V |
21 |
1~5 V square root |
02 |
S |
06 |
J |
10 |
Cu50 |
15 |
0~5 V |
22 |
0~5 V square root |
03 |
K |
07 |
WRe3~25 |
12 |
4~20 mA |
19 |
4~20mA square root |
||
04 |
E |
08 |
Pt100 |
13 |
0~10 mA |
20 |
0~10mA square meter |
Alarm output mode
Selection code |
N |
H |
L |
G |
A |
D |
E |
output method |
No alarm (can be omitted) |
upper limit alarm |
Lower limit alarm |
Deviation internal alarm |
Deviation outside alarm |
LBAcall the police |
End alarm |
Transmission output mode
Selection code |
0 |
1 |
2 |
3 |
4 |
5 |
output method |
No output |
relay |
4~20mA |
0~10mA |
1~5V |
0~5V |
contact method
Selection code |
0 |
2 |
4 |
8 |
9 |
contact method |
No communication |
RS-232 |
RS-422 |
RS-485 |
special specifications |
Control output mode
Selection code |
0 |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
output method |
No output |
relay |
4~20mA |
0~10mA |
1~5V |
0~5V |
SCRoutput |
SSRoutput |
special specifications |
SOToutput |