On load tap changer tester I-1A, required for power qualification

NegotiableUpdate on 01/22
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

1、 Please read the instruction manual carefully before testing the product overview; To ensure accurate testing, please demagnetize the power transformer or conduct a DC resistance test before using this instrument. The transformer on load tap changer characteristic tester is a comprehensive measuring instrument used to measure and analyze the electrical performance indicators of power transformers and special transformer on load tap changers in power systems. It is computer-controlled and connected to

Product Details

1、 Product Overview

Please read the instruction manual carefully before testing;

To ensure accurate testing, please demagnetize the power transformer or conduct a DC resistance test before using this instrument.

Transformer on loadtap-offswitchfeatureA tester is a comprehensive measuring instrument used to measure and analyze the electrical performance indicators of power transformers and special transformers on load tap changers in power systems. It adopts computer control and can realize the measurement of on load tap changers through specially designed measurement circuitstransition timeTransition waveformTransition resistanceThree phase synchronicityThe measurement of parameters such as, can be directly measured by the tap changer leads according to the needs and site conditions, or by the transformer three-phase bushing and neutral point direct wiring measurement.

This instrument has functions such as analyzing, storing, and printing the measured data. Solved the problem of outdated measurement methods and lack of testing methods for on load tap changers in current power transformers. It can timely diagnose potential faults in on load tap changers during preventive testing of power equipment and transformer maintenance, which is of great significance for improving the reliability of power system operation.

The instrument has a high degree of intelligence, with all Chinese menu prompts and simple operation. The instrument has a small volume, light weight, and strong resistance, greatly reducing the labor intensity of on-site workers. It is an ideal instrument for power generation and supply units, transformer manufacturing industry to ensure safety production and improve product quality.

2、 Functional Features

lThe instrument has a high output current and is lightweight;

lThe instrument outputs an open circuit voltage of 30V and can test a transition resistance of 30 Ω at a current of 1A,

lCan automatically calculate the transition resistance value and transition time value;

lEquipped with comprehensive protection circuits and strong reliability;

A 5.7-inch large LCD display for easy on-site operation;

lIt has storage function and can analyze data waveforms.

3、 Technical parameters

Output current 1.0A

Measurement range: Transition resistance: 0.5Ω40Ω

Transition time: 0-250ms

Measurement accuracy transition resistance: ± (5% reading+3 words)

Transition time: ± (0.1% reading+3 words)

Dimensions: 340mm × 245mm × 210mm

Instrument weight 7kg

4、 Usage conditions

Environmental temperature -10 ℃~50 ℃

Environmental humidity ≤ 85% RH

Working power supply AC220V ± 10%

Power frequency 50 ± 1Hz