Welcome Customer !

Membership

Help

Jiangsu Zhongyang Electric Co., Ltd
Custom manufacturer

Main Products:

mechb2b>Products

Multi functional high-voltage switch dynamic characteristic tester

NegotiableUpdate on 01/23
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The multifunctional high-voltage switch dynamic characteristic tester is a newly designed instrument for detecting the mechanical dynamic characteristics of high-voltage circuit breakers. This instrument adopts high-tech technology and integrates computer, printer, measurement interface circuit, and operating power supply. It is a new instrument for detecting high-voltage circuit breakers.

Product Details

Multi functional high-voltage switch dynamic characteristic tester

The testing instrument is equipped with two types of displacement sensors suitable for different distances and accuracy tests. The instrument's automatic recognition system identifies the selected sensors and completes distance and speed measurement for low oil, high oil, sulfur hexafluoride, and vacuum high-voltage circuit breakers. In terms of instrument design, only one closing (opening) action is needed to sample and record all the data of six fracture surfaces, display the measurement results with a single key operation, and print the recorded measurement data. It can also print the current waveform of six fracture surfaces and the time characteristic curve of one fracture surface's moving contact.

Features and Characteristics
1. Testing function
⑴ Simultaneously measure one to six fracture surfaces in the order of closing (opening) the circuit breaker
⑵ Simultaneously measure one to six fracture surfaces in different phases of the three-phase system in milliseconds
⑶ Simultaneously measure one to six fracture surfaces in the same phase but different periods in milliseconds
⑷ Simultaneously measure the closing (opening) time of one to six fractures in milliseconds
⑸ Simultaneously measure the bounce time of one to six break surfaces in milliseconds when closing (opening) the circuit breaker
⑹ Measure the closing (opening) speed of a fracture surface in m/s
⑺ Measure the closing (opening) speed of a fracture surface in m/s
⑻ Measure the average speed of closing (opening) the switch at a fracture point in m/s
Simultaneously measure one to six fracture surfaces in mm for the travel of the moving contact
Measure one to six fracture surfaces in mm at the same time when the moving contact exceeds the contact stroke
⑾ Opening and closing time (metal short-circuit time) ms
12. No current time (automatic reclosing no current interval time) ms
2. Main Performance and Characteristics of High Voltage Switch Mechanical Characteristics Tester
The instrument adopts highly stable components. Floating, large-area, digital filtering and other anti-interference technologies.
The instrument is equipped with two types of displacement sensors, suitable for detecting high-voltage circuit breakers with different distance, speed, and accuracy requirements. After inserting different sensors, the instrument will automatically recognize them. The instrument can automatically recognize the closing (opening) and reclosing operations of high-voltage circuit breakers, and automatically collect all kinds of data after the operation. The measurement and calculation process is automatically completed by the CPU.
The instrument has the ability to automatically identify wiring errors, incorrect instructions, and unsuccessful operations during the measurement and operation of high-voltage circuit breakers, as well as strong self-protection functions.
The instrument displays the order of closing (opening) and the actual closing (opening) time of each break, providing a basis for the maintenance and debugging of high-voltage circuit breakers in different phases and phases. The data related to time quantity is automatically not displayed and output in 0.1 milliseconds.
⑸ The instrument can measure the travel and overtravel of the moving contact by installing sensors on the fracture surface of any phase of the high-voltage circuit breaker, and can simultaneously measure and calculate the travel and overtravel data of each fracture surface of the three phases. The instrument has a measurement accuracy of 1% per second for speed.
The power box provides a 0-250V DC operating power supply to directly operate the high-voltage circuit breaker. Suitable for DC controlled operating mechanisms such as electromagnetic, hydraulic, and spring energy storage.
The instrument is small in size, light in weight, easy to operate, and portable, especially suitable for field flow detection and on-site maintenance and testing of substations. It is a tool for the production, inspection, maintenance, and commissioning of high-voltage circuit breakers.

Multi functional high-voltage switch dynamic characteristic tester

technical indicators
1. Comprehensive technical indicators
External operating power supply voltage of the instrument: AC/DC 48V~280V
Output operating mechanism voltage: AC/DC 48V~280V
Simultaneously measurable number of fractures: 1-6
Distance from host to measurement accuracy and error sensor: 10 meters for mechanical sensors
Vacuum sensor 5 meters
Working power supply: AC 220V; 50Hz 0 ± 10%
Working environment temperature: -0 ℃ to+40 ℃
Power: < 55W
Weight: 5kg host