DZ47LED-63 lightning protection residual current circuit breaker

NegotiableUpdate on 07/09
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

1、 Scope of application

Product Details

1、 Scope of application

DZ47LED-63seriesLightning protection leakage switch(Lightning protection residual current circuit breaker)It is a small device with lightning protectionLeakage circuit breakerSuitable for lightning protection, surge protection, leakage protection, short circuit protection, and overload protection in distribution networks with AC voltage of 380V and below and frequency of 50Hz. And it can be used for infrequent switching of lines under normal circumstances.
Implementation standards for lightning protection residual current operated circuit breakers (RCBOs) with overcurrent protection for household and similar use: GB16917.1 Part 1: General rules GB188022 IEC61643-1 and GB 500057 "Code for Design of Lightning Protection of Buildings".

2、 Model and its meaning

3、 Structural characteristics

The lightning protection residual current switch is composed of a surge protection module (SPD) added to a small residual current circuit breaker, which has relative ground and neutral to ground protection modes. Especially suitable for situations that require multiple protections. This product consists of three SPDs and one gas discharge tube BL forming the main discharge circuit. The three SPDs are connected in series with the L1, L2, and L3 poles (live) and the N pole (neutral) of the gas discharge tube, and then connected to the earth (PE) to discharge lightning through the earth (PE), thus protecting the load end of the switch from lightning damage. During normal operation, the green light is on and the red light for fault issues is on.

4、 Product Features

1. It has lightning protection, leakage protection, overload protection, and short circuit protection functions.
2. It has lightning protection and grounding function.
3. It has full mode protection for phase to neutral, phase to ground, and neutral to ground wires.
4. It has lightning protection fault indication function.
5. The maximum lightning current capacity is 20KA.
6. There is an overheat protection device inside.
7. The switch adopts two-level lightning protection inside.
8. External alarm signals can be used.

5、 Main technical parameters

Rated current: 6, 10, 16, 20, 25, 32, 40, 50, 63A
Rated working voltage: 230/400V AC
Rated insulation voltage: 500V
Rated residual operating current: 30, 50, 75, 100, 300 mA
■ Tripping indicator: There is a residual current action tripping indicator on DZ47LE, and the reset button pops up, indicating leakage tripping
■ Manual control: The handle allows for two reset modes
Overcurrent fault: circuit breaker and residual current action device reset simultaneously
Leakage fault: residual current action device resets first, circuit breaker resets later
□ Lightning protection fault: The lightning protection device is reset first, followed by the circuit breaker
Mechanical lifespan: 10000 cycles
Electrical lifespan: 2000 cycles
Compliant with standard: IEC61009-1/GB16917.1
■ Compliant with certification: CCC certification
■ Release characteristics
C-type tripping characteristic: Curve protection for conventional loads and distribution cables, instantaneous tripping range (5-10) In
D-type tripping characteristic: protects against high starting current impact loads (such as transformers), with an instantaneous tripping range of (10~14) In

model DZ47LED-63
number of poles 1P+N 3P+N
Shell level rated current lnm (A) 63
neutral pole N
Rated current ln (A) 6,10,16,20,25,32,40,50,63
Rated working voltage (V) 380(400)
Rated short-circuit breaking capacity 4500A
Rated leakage current l △ n (mA) 50
Rated leakage non operating current l △ no (mA) 25

Note: * D-type and l △ n=50mA are regular supply products, unless otherwise specified. Please contact us for C-type and other leakage action currents.

6、 Lightning protection parameters

Model specifications DZ47LED-63
Working voltage Un (V) 380
Maximum flow rate Imax (kA) 15
Nominal flow rate In (kA) 10
Response time t (ns) <25
Connecting multiple copper wires to the grounding terminal 6mm²

Note: ① Lightning protection leakage switch is designed for induction lightning; ② Lightning protection residual current circuit breakers are used indoors; ③ The grounding resistance of the ground wire should be as small as possible, less than 10 Ω.

7、 Overcurrent tripping characteristics

Serial Number Rated current In (A) Release type Initial state test current Set time t Expected results notes
a 6~63 C、D cold state 1.13In t≤1h Do not release
b 6~63 C、D Immediately following the previous paragraph
Experiment conducted
1.45In t<1h trip The current remains stable within 5 seconds
Rise to the specified value
c 6~63 C、D cold state 2.55In 1s<><>< td=''> <><> trip
1s<><120s(in>32A)<120s(in>120s(in>120s(in>
d 6~63 C cold state 5In t≥0.1s Do not release Close the auxiliary switch
switched on
D 10In
C 10In t<0.1s trip
D 50In

8、 Usage and maintenance

1. The lightning protection, leakage, overload, and short-circuit characteristics of lightning protection residual current circuit breakers are set by the manufacturer and are not allowed to be adjusted arbitrarily during use.
2. Lightning protection residual current circuit breakers must be tested by pressing the test button before being installed or used again after a power outage to ensure normal tripping. Under normal use, they must be tested for tripping once a week.
3. When using electric tools and equipment within the protection range of lightning protection leakage switches, the test button must be pressed to ensure normal tripping before they can be put into use.
4. After humid weather or thunderstorms, the test button must be pressed before each use to ensure normal tripping before being put into use.
5. If the lightning protection leakage switch has a fault or cannot trip by pressing the experimental button, please stop using it immediately and send it back to the manufacturer for repair as soon as possible.
6. After the lightning protection leakage switch is opened due to a malfunction of the brake system, the cause must be identified and the fault must be eliminated before it can be closed.
7. The lightning protection leakage switch cannot provide protection against the risk of electric shock caused by simultaneously touching two wires of the protected circuit.
8. According to the national standard, the function of a leakage protector is to provide indirect contact electrical protection. When other protective measures fail... it cannot be used as the only direct contact protection.

9、 Appearance and installation dimensions


Product size A B C D 1P+N 3P+N
DZ47LED-63 39 30 21 6 18+27 54+45