DZ47LE-63 household residual current circuit breaker

NegotiableUpdate on 07/09
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

1、 Scope of application

Product Details

1、 Scope of application

DZ47LE-63seriesLeakage circuit breakerThe residual current circuit breaker (hereinafter referred to as RCCB) is suitable for use in circuits with AC 50Hz, rated voltage up to 400V, and rated current up to 50A. It is used for leakage and overload protection, to prevent fire or personal injury accidents caused by circuit leakage or electric shock, and can also provide overvoltage protection against excessive voltage rise caused by power grid failures.
The DZ47LE-63 series residual current circuit breaker is a current operated electronic residual current circuit breaker, consisting ofDZ47 circuit breakerCombined with residual current release device. When there is leakage or personal electric shock in the protected circuit, as long as the leakage current I △ reaches the operating current value, the circuit breaker will immediately operate, cut off the power supply, and thus play a role in leakage and electric shock protection. At the same time, the leakage circuit breaker can also protect against overload and short circuit in the circuit.
Circuit breakerMeets the requirements of standards such as IEC61009-1:1996 and GB16917.1 "Residual Current Operated Circuit Breakers with Overcurrent Protection for Household and Similar Purposes (RCBO) Part 1: General Rules".

2、 Model and its meaning

3、 Normal working and installation conditions

The altitude does not exceed 2000 meters;
The ambient air temperature should not exceed+40 ° C, not be lower than -5 ° C, and the average value within 24 hours should not exceed+35 ° C;
The relative humidity at the installation site should not exceed 50% at a maximum temperature of+40 ° C. Higher relative humidity is allowed at lower temperatures, such as up to 90 ° C at 20 ° C, taking into account condensation on the product surface due to temperature changes;
Installation conditions: Install in a place without impact, vibration, or rain or snow invasion; In a medium without explosive hazards, and without gases and conductive dust that can corrode metals and damage insulation;
Pollution level: 2;
Installation category: III;
The electromagnetic environment is environment B;
The external magnetic field of the installation site should not exceed 5 times the geomagnetic field in any direction;
■ Installed using standard installation rails (TH35-7.5), installed in distribution boxes, cabinets or boxes;
During installation, it is generally installed vertically, with an inclination of no more than ± 5 ° between the installation plane and the vertical plane, and the handle facing upwards as the power on position.

4、 Main technical parameters

Rated current: 6, 10, 16, 20, 25, 32, 40, 50, 63A
Rated working voltage: 230/400V AC
Rated insulation voltage: 500V
Rated residual operating current: 30, 50, 75, 100, 300 mA
■ Tripping indicator: There is a residual current action tripping indicator on DZ47LE, and the reset button pops up, indicating leakage tripping
■ Manual control: The handle allows for two reset modes
Overcurrent fault: circuit breaker and residual current action device reset simultaneously
Leakage fault: residual current action device resets first, circuit breaker resets later
Mechanical lifespan: 10000 cycles
Electrical lifespan: 2000 cycles
■ Wiring
□ 6-32A, can connect wires of 16mm ² and below
□ 40~60A, can connect wires of 25mm ² and below
Compliant with standard: IEC61009-1/GB16917.1
■ Compliant with certification: CCC certification
■ Release characteristics
□ C-curve
Protect conventional loads and distribution cables
Release characteristics: instantaneous release range (5-10) In
D-type curve
Protect impulse loads with high starting current (such as transformers, etc.)
Release characteristics: instantaneous release range (10~14) In

Rated shell level
Current Inm (A)
number of poles Add Central
Sexual line
Rated current
In(A)
Rated residual
action current
(mA)
Rated residual
Not moving electricity
Current (mA)
Rated short-circuit breaking capacity Rated residual
Connect and disconnect
Ability (A)
Overcurrent transient
Time release type
Voltage (V) On-off capability cosΦ
32 1 N (breakable) 6. 10
16. 20

25, 32
30 15 230 4500A 0.8 2000 C
63 1 N 30, 50
75, 100
15. 25
38, 50
230 6000A 0.7 2000 B、C、D
2
3
3 N
4
400
1 N 40, 50
、 sixty-three
30, 50
75, 100
15. 25
38, 50
230 4000A 0.8 2000 B、C、D
2
3
3 N
4
400

Installation of DZ47LE-63

Current level (A) screw Rated torque of screw (N.m) Ultimate torque (N.m) Standard torque (N.m)
6~32 M4 2.0 3.0 1.2
40~60 M5 2.5 4.5 2.0

DZ47LE-63 breaking capacity

Rated current (A) Release curve
C D
6~40 6 4
50, 60 4 4

Protection features

1. In addition to having leakage protection function, residual current circuit breakers can also protect against excessive voltage rise caused by power grid faults. The overvoltage setting value Uvo=280V and the setting range Uvo ± 5% (used in AC230V rated voltage lines).
2. Protection characteristics of overcurrent release device

Type of release device C D tripping time
Thermal trip I1 1.13In 1.13In ≥1h
I2 1.45In 1.45In <1h
Magnetic release I4 5In 10In ≥0.1s
I5 10In 20In <0.1s
In(A) I△n(A) When the residual current is equal to the following value, the interruption time (s)
I△n 2I△n 5I△n 5A,10A,20A,50A,
100A,200A,500A
I△tb





0.04 0.04

Note: a. The tests for 5A, 10A, 20A, 50A, 100A, 200A, and 500A are only conducted to verify the action and do not test current values greater than the lower limit of the instantaneous tripping range of overcurrent.
b. Conduct the test at the current value that is equal to the lower limit of the instantaneous tripping range of overcurrent for type C or D when I △ t is equal to it

Serial Number Rated current In (A) Release type Initial state test current Set time t Expected results notes
a 6~60 C、D cold state 1.13In t≤1h Do not release
b 6~60 C、D Immediately following the previous paragraph
Experiment conducted
1.45In t<1h trip The current remains stable within 5 seconds
Rise to the specified value
c 6~60 C、D cold state 2.55In 1s<><>< td=''> <><><60s(in≤32a)<> trip
1s<><120s(in>32A)<120s(in><120s(in>120s(in>120s(in>
d 6~60 C、D cold state 5In t≤0.1s Do not release Through closed assistance
Switch reading current
C、D 10In t<0.1s trip
C、D 10In t≤0.1s Do not release Through closed assistance
Switch reading current
C、D 16In t<0.1s trip

DZ47LE-63 Mechanical and Electrical Life

project Number of projects (times) operating frequency
Electrical life 2000, cosφ=0.85~0.9 In≤25A, 240 times/h; In>25A, 120 times/h
mechanical life 10000

Correction coefficient of current at different environmental temperatures

Temperature ℃ -15 -5 0 10 20 30 40 55
Rated current correction factor 1.19 1.15 1.13 1.06 1.05 1 0.96 0.89

Wiring: The DZ47LE-63 residual current circuit breaker (100A residual current switch, three-phase residual current protection switch) is suitable for connecting wires of 25mm ² and below. The wiring method is to tighten the wiring with screws, with a torque of (1.5~2.0) N.m.

Rated current In (A) Nominal cross-sectional area of copper wire (mm ²)
6 1
10 1.5
16. 20 2.5
25 4
32 6
40, 50 10
63 16

5、 Circuit breaker trip characteristic curve

6、 Appearance and installation dimensions

Product size A B C D 1P+N 2P 3P 3P+N 4P
DZ47LE-63 39 30 21 6 18+27 36+24 54+27 54+45 72+45

7、 Wiring diagram