Simplify complexity into a truly integrated product
Reduce on-site workload, minimize leakage points, and save overall investment
Using a transmitter with excellent performance
Durable and sturdy, improving production efficiency
Standardized design ensures measurement accuracy and consistency
2D before and after the straight pipe section
Reduce signal distortion and improve measurement accuracy
Improve process control accuracy and increase yield
Low pressure loss, saving operating costs
Complete configuration and testing within the factory
Measurement medium: suitable for measuring liquids, gases, and vapors, standard structure is not suitable for strong corrosive, high viscosity, easy to crystallize, and dirty media
Medium temperature: gas, liquid: -40-250 ℃; Steam: below 550 ℃, condensation device added
Instrument size: DN15-DN600
Uncertainty: System reference accuracy ± 1.0%
Range ratio: 7:1-10:1
Pressure loss: 10-30% DP
Straight pipe section: Front 2D+Rear 2D
Power supply: Two wire 24V DC circuit power supply
Output signal: 4-20 mA+HART
Communication: HART protocol, subject to specific configuration
Explosion proof level: higher than Ex ia IIC T4 and Ex d IIC T6 explosion-proof levels, subject to actual configuration
Display: LCD screen, displaying differential pressure or percentage
Instrument material: determined according to actual design requirements
Process connection: The standard is flange connection, with optional clamping and welding structures
Connection standard: Complies with ANSI/HG20615 CL150-CL600 lb, DIN/HG20592 PN10-PN100 bar
Installation location: default is horizontal installation, vertical installation requires customization
Special application: Oxygen adopts oil free degreasing process, and the transmission unit is filled with inert liquid
Installation of gas flowmeter
Within a 45 degree angle range vertically upwards, left and right, to prevent liquids and foreign objects from entering the pressure tube

Installation of liquid flowmeter
The header is located below the pipeline, within a 45 degree angle range horizontally downwards, to prevent gas from entering the pressure pipe

Installation of steam flowmeter
The pressure tap is located above the pipeline, within a 45 degree angle range from horizontal to upward. The condenser tank is located at the point, the condenser tube is in a vertical state, and the transmitter is located below the condenser tank or pipeline. The standard structure is only applicable to horizontal pipelines and is strictly prohibited from being used for vertical pipelines