I. Overview
The DC resistance of transformers is a necessary test item for semi-finished and finished products in transformer manufacturing, factory testing, installation, handover testing, and preventive testing by the power department. It can effectively detect manufacturing defects such as material selection, welding, loose connection parts, missing strands, and broken wires of transformer coils, as well as hidden dangers after operation. In order to meet the needs of rapid measurement of transformer DC resistance, our company has developed a DC resistance tester using our own technological advantages. This instrument adopts a new power technology, which has the characteristics of small size, light weight, high output current, and can automatically adjust according to the load size.ZYZ-10A AC/DC Resistance TesterThe whole machine is controlled by a microcontroller, which automatically completes self checking, data processing, display, printing and other functions, and has automatic discharge and discharge indication functions. The instrument has high testing accuracy, easy operation, and can achieve rapid measurement of transformer direct resistance.
2、 Security measures
1. Before using this instrument, be sure to read this manual carefully.
2. The operator of the instrument should have general knowledge of using electrical equipment or instruments.
3. This instrument can be used both indoors and outdoors, but should be kept away from places such as rain, corrosive gases, excessive dust, high temperatures, and direct sunlight.
4. Instruments should avoid severe vibrations.
5. The maintenance, care, and adjustment of instruments should be carried out by professionals.
6. After the test is completed, be sure to wait for the discharge alarm to stop before turning off the power and removing the test line.
7. When measuring an unloaded voltage regulating transformer, be sure to wait for the discharge indicator alarm sound to stop before switching gears.
8. During the testing process, it is prohibited to move the test clamp and power supply line.
3、 Performance characteristics
1. The instrument has a large output current, wide measurement range, small size, and light weight.
2. The current output automatically adjusts the current according to the measured resistance value, so that it jumps to the appropriate range, avoiding errors caused by improper current selection.
3ZYZ-10A AC/DC Resistance TesterIt has a complete protection circuit and strong reliability.
4. Vertical chassis structure, convenient for on-site operation.
5. Equipped with sound discharge alarm, clear discharge indication, and reduced misoperation.
4、 Technical indicators
1. Output current: 200mA~20A using constant current source (20A/28V automatically selects current based on resistance)
2. Range: 2A-400 mA (1 Ω -100 Ω± 0.2% ± 5 words)
10A (100M Ω -1 Ω± 0.2% ± 2 words)
20A (1M Ω -200M Ω± 0.2% ± 2 words)
3. Accuracy: ± 0.2% ± 2 words
4. Resolution: 1 μ Ω
5. Working temperature: 0-40 ℃
6. Environmental humidity: ≤ 90% RH, no condensation
7. Working power supply: AC220V ± 10%, 50HZ ± 1HZ
8. Volume: 425 × 285 × 270mm
9. Weight: 9 Kg (excluding testing line)