Supply pressure large screen display instrument, large screen fast pressure acquisition, the most powerful high-value recorder, with a transmission output of 0-20mA

NegotiableUpdate on 02/08
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin
Overview
YK-LED4 series intelligent large screen display controller $r $n1, power supply: AC220V, 24V, 12V, 5V, 3.3V selectable. $r$n2、 Output: RS485 communication, analog 4-20mA, relay alarm output, feed output 24V/200mA $r $n3, input signal, internal parameter switching input, thermal resistor PT100, -200 ℃~500 ℃, CU50$r$n4、 Thermocouple K-type, voltage and current 0-20mA, 4-20mA, 0-5V, 0-10V
Product Details

YK-LED

Intelligent large screen digital display instrument

(Instructions for use)

I. Overview

This series of products adopts surface packaging modular technology, greatly improving the resistance of instruments. It has functions such as display, control, transmission, communication, and signal input, and is suitable for displaying and controlling various physical quantity detection signals such as temperature, humidity, pressure, liquid level, instantaneous flow rate, and speed. It can also perform high-precision linear correction on various nonlinear input signals. It can be widely used in fields such as electricity, metallurgy, chemical industry, petrochemicals, paper printing and dyeing, brewing, tobacco, aerospace bases, etc.

By adopting jumper free technology, the input port is equipped with * signal input function. By changing the internal parameters, multiple input signals (various thermocouples, thermal resistors, remote pressure, mV, standard voltage/current signals) can be easily switched between. The circuit board has been optimized in design and continuously improved in production process, reducing temperature drift and enhancing anti-interference performance to ensure the stability and reliability of the product during operation. Adopting high brightness LED digital display and high-resolution light column display (proportional display), the display of measurement/control values is clearer and more intuitive.

The output circuit adopts photoelectric isolation, which has strong resistance. It can be equipped with a serial communication interface and can communicate bidirectionally with various devices with serial interfaces to form a network control system. It has multiple standard external dimensions and can be applied to various measurement and control scenarios. The whole machine adopts a snap in structure, which is very easy to install.

  • Scope of Application

This series of intelligent temperature display screens is used in boiler rooms, bathhouses, hot springs, plazas, banks, etc.

  • Features

*Input function

Automatic calibration and manual calibration functions

Multiple protection, isolation design, strong resistance, high reliability

A good software platform with secondary development capabilities to meet special functions

*The modular structure, combined with powerful instrument chips, makes it very convenient to combine functions and upgrade systems

2、 Main technical indicators

Basic error:0.2FS14bitA/DConverter (the largest)18bitA/DConverter, specify when ordering).

Input signal: thermocouple: BTheSTheKTheETheJTheTTheWRewait

·Thermal resistance: Pt100TheCu50TheCu53TheCu100TheBA1TheBA2

·Current010mA420mAWait (input impedance ≤250Ω)

·Voltage05VThe1V5VThemVWait (input impedance ≥)1MΩ)

·Remote transmission pressure resistor:(0400(Ω)

Sampling period0.2S10~200time/Seconds, user selectable)

Display: Single row four position LED, 3-inch digital display

Alarm output: The instrument can be equipped with multiple relay outputs, with relay contact capacity of AC220V/5A or AC220V/1A. Zui can carry up to 16 relays,Upper and lower limit control can be selected, and the control set value and hysteresis value can be freely set within the full range

Transmission output: 4-20mA, 0-10/20mA (load resistance ≤ 250 Ω, indicate if the load is too large)

1-5V, 0-5V, 0-10V (load resistance ≥ 200K Ω).

adopt12 bit digital D/A chip, isolated output.

Communication output: Isolated communication interface RS485/RS232 baud rate 1200-9600bps

Feed output: DC24V/30mA, DC12V/30mA

Temperature compensation: 0-50 cold end temperature automatic compensation, error: ± 1 ℃

Power supply: Switching power supply 85-265VAC or DC24V or DC12V

Power consumption: 4W

Environmental temperature:(-2070)℃ (Start up and run at room temperature)30minutes later,Can gradually withstand extreme temperatures)

(0~50)℃ (thermocouple signal input)

Relative humidity: ≤ 85%. No condensation. Avoid use in corrosive and flammable/explosive gases

Panel size: 3400mm in length, 2200mm in width, 60mm in depth, excluding pendants.

Our company independently develops and produces various types of instruments with complete functions, such asUsers can choose fast sampling, with the fastest speed of 200 times per second, high-precision 18 bit A/D acquisition, high-precision 16 bit D/A output, input signal 20 segment curve correction, full 5 or 6 bit display, LCD display, special input signal, multiple relay alarm buzzer outputs, high-power feeding output, etcPlease specify when placing an order

3、 Model Description

YK-LED

Intelligent large screen digital display device

Overall dimensions

34

3inch4Digital display tube, horizontal 340×220×60mm

56

5inch6Digital display tube, horizontal 1000×300×800mm

84

8inch4Digital display tube, horizontal1000×300×800mm

104

10inch4Digital display tube, horizontal 1000×300×800mm

Screen selection

DP

Single sided screen display

SP

Double sided screen display

alarm output

J

J0-J40-4Point alarm output (most available)16A relay)

K

K0-K40-4aSSRoutput

transmitter output

O1

4-20mAoutput(Zui Duo8Road analog output)

O2

0-10mAoutput(Zui Duo8Road analog output)

O3

1-5Voutput(Zui Duo8Road analog output)

O4

0-5Voutput(Zui Duo8Road analog output)

O5

0-10Voutput(Zui Duo8Road analog output)

Communication output

P

mini printer

R

Serial communicationRS232

S

Serial communicationRS485

Wireless communication (accessible)1000Rice)

Distribution power supply

V12

beltDC12VFeed output

V24

beltDC24VFeed output

power supply

220VACpower supply

W

DC24Vpower supply

buzzer

FM

Buzzer alarm, intermittent sound

input signal

()

Refer to the input type table, such asPT100Input, can be directly written after the model numberPT100

Model example: YK-LED-84-DP-J2-O1-S-V24-FM (4-20)

YK-LED large screen display device,8inch4Digital display tube,Exterior dimensions: Horizontal 900×300×100mm(excluding hooks), single row4Position display, two relay alarm control outputs,4-20mA transmission output with RS485 isolated communication interface,beltDC24VFeed output,Input signal 4-20mA,power supply85~265VAC, Equipped with buzzer alarm.

Attention: The large screen produced by our company can be used in conjunction with various signals, such as strain gauges, pressure transmitters, encoders, etc,BCDCode, liquid level sensor, etc. Can consult technical engineer: Zhang Shuguang

4、 Operating instructions

(1)Key function, the product is equipped with an infrared remote control, and when setting parameters, simply aim at the screen (within 5 meters). If the infrared remote control is lost, the back cover can be opened, and there are four backup buttons designed inside.

Set value shift key, used to move the set value bit in the set state.

When setting the state, switch the prompt and switch the set value.When the instrument panel is equipped with a buzzer function, pressing this button during operation can silence the sound, and it can return to the set state.

Parameter setting key, used to store the new set value of the parameter and enter the next one when in the setting state

Set parameters.

Set value increase key, used to increase the numerical value when in the set state.

Set value increase key, used to decrease the numerical value when in the set state.

(II)Power-On Self-Test

Connect the wiring of the instrument according to the terminal diagram, and only turn on the power after it is correct.After the instrument self-test, if it displays -, it indicates that there is no signal received, the input signal exceeds the range, or the input signal type is set incorrectly. The instrument adopts a human-machine dialogue form to input parameters, and various prompts are used to indicate the data that should be input.

(3) Parameter setting

In working mode, the upper row displays the measured values, while the lower row displays them according to the settings. In the set state, the instrument displays a parameter prompt, press to display the set value. If during the setting process15If the parameter remains unchanged for a second, the instrument will automatically return to operation. Set a parameterAfterwards, press En againPress the key to confirm and enter the next parameter setting state.

The parameter settings are as follows:

(1)pressEnKey, the upper display window appearsLocThe lower display window showsoFFYou must press the ▲ key tooFF改成onOnly after that can the alarm point setting value be modifiedLocset asoFFAt this time, the alarm point setting value cannot be modified and can only be browsed.

(2) J1HAJ1Relay alarm point setting value(whenJ1-Hset asOFFIf so, this option will be closed).

(3)J1HFJ1Relay alarm reset value(whenJ1-Hset asOFFIf so, this option will be closed).

(4) J2HAJ2Relay alarm point setting value(whenJ2-Hset asOFFIf so, this option will be closed).

(5) J2HF: J2 relay alarm reset value (this item is turned off when J2-H is set to OFF).

Set sequentiallyJ3TheJ4The alarm parameters.

After the alarm settings are completed, a password is required to enter the secondary parameter settings.

(6)cd- Password, use ▲ orThe key will800set to808,press againEnThe key is used to enter the parameter setting state, and entering other values is invalid to prevent non-technical personnel from misoperation. After setting a parameter, pressEnPress the key to set the next parameter.

(7) SnInstrument input signal type.

Note: Input signal selection comparison table(Free input is automatically completed internally, without the need for hardware adjustment, and the mA signal does not require a resistor. )

Parameter prompt

Input signal type

Parameter prompt

Input signal type

tc―K

Ktype

rtd

resistance0-400Ω

tc―S

Stype

bA1

BA1

tc―E

Etype

bA2

BA2

tc―b

Btype

050

050mV

tc―t

Ttype

05V

05V

tc―n

Ntype

15V

15V

tc―J

Jtype

020

020mA

P100

Pt100

010

010mA

C100

Cu100

420

420mA

Cu50

Cu50

Please specify other input signals when ordering

(8) dot- Decimal point position, range03, such asdot=2, the display format isXX. XXFor temperature signals such as thermistors and thermocouples, the maximum setting is1The display resolution is0.1, in1000Automatic conversion above degreeresolutionfor1.

(9) inPLThe lower limit of the linear input corresponds to the displayed value, which is the lower limit of the instrument range-1999~9999.

(10) inPHThe upper limit of the linear input corresponds to the displayed value, which is the upper limit of the instrument range-1999~9999.

(11)J1-HJ1Relay alarm mode. set as-HH-Indicates an alarm for excessively high measurement values (upper limit alarm), set to-LL-Indicates a measurement value ultra-low alarm (lower limit alarm), set toOFFThis indicates that the alarm is prohibited at this point.(Alarm reference Alarm Description)

Set sequentiallyJ2TheJ3TheJ4The alarm method.

(12) bS- Transmission output mode, selectable1~5V、0~5V、420mA0~10mA0~20mASeveral ways.

(13) bS-L­The instrument measurement display value corresponding to * under the transmission output.

(14) bS-HThe instrument measurement display value corresponding to the * on the transmission output. (See the sixth item "Transmission Output" later)

(15) oSEt- Zero point correction coefficientAfter correction, the displayed value is equal to the measured value before correction plus oSEt. The factory value oSEt is 0.0

(16)FSEt - The range of the full-scale correction coefficient is 0.500 to 2.000. After correction, the displayed value is equal to FSEt × (measured value before correction+oSEt), and the factory value FSEt is 1.000.

(17)Lb- Digital filtering parameters, set within the range of030.LbThe larger, the more stable the measurement value, but the response

It's also slower. Generally, when the measured value is subjected to significant interference, it can gradually increaseLbAdjust the values so that the fluctuation between measured values is less than25One word. When conducting metrological calibration of instruments in the laboratory, it is necessary toLbset to0or1To improve response speed. factory default3.

(18) Addr- Communication address and range of the instrument199.

(19) bAUd- Communication baud rate, range1200~9600.

Parameter setting completed, display-EndThe instrument automatically enters the running state.

5、 Alarm

This instrument can be equipped with multiple relays, each of which can be set with ultra-high, ultra-low alarm, and prohibition alarm modes, and adoptsThe alarm return method avoids frequent relay actions. When a relay is in an alarm state, the corresponding relay's normally open contact is closed and the corresponding indicator light is on. withJ1Example of alarm point alarm:

If the alarm mode of this alarm point is set to upper limit alarm (i.eJ1-Hset as-HH-)When the measured value is greater thanJ1HAWhen the instrument enters an alarm state, the measured value drops toJ1HAThe instrument does not stop alarming when the value is reached, only when the measured value is belowJ1HFAt this time, the instrument will only release the alarm state. When set as the upper limit alarm, the alarm valueJ1HATo be greater than the alarm reset valueJ1HF.

If the alarm mode of this alarm point is set to lower limit alarm (i.eJ1-Hset as-LL-)When the measured value is less thanJ1HAWhen the instrument enters an alarm state, the measured value rises toJ1HAThe instrument does not stop alarming when the value is reached, only when the measured value is higher thanJ1HFAt this time, the instrument will only release the alarm state. When set as the lower limit alarm, the alarm valueJ1HABe less than the alarm reset valueJ1HF.

6、 Transmission output

The instrument can convert the measured value into a standard signal, and the output form is determined byThe "bS" parameter is determined, and the measurement value transmission range is determined by the "bS-L" and "bS-H" parameters. If measuring temperature signal PT100, it is required to output 4.0mA at 0 ℃ and 20.0mA at 150 ℃, then bS=4-20, bS-L=0.0, bS-H=150.0. So when the instrument displays 75.0 ℃, it outputs 12.0mA.

sevenCommunication instructions

This instrument can be equipped with RS232 and RS485 interfaces for direct communication with computers,RS485 standard communicationdistance1.5kmMultiple instruments can be attached.RS232 standard communicationdistance15mOnly one instrument can be attached.The TXD, RXD, and GND of the RS232 interface are respectively connected to the second, third, and fifth pins of the computer serial port. The data format consists of 1 starting bit, 8 data bits, and noneverify1A stop position.

This device adopts the standard Modbus RTU communication protocol and can be connected to almost all configuration software, including Kingview, Power Control, Century Star, etc Fix、InTouchWaiting for domestic configuration software eliminates the hassle of users connecting to the softwareWhen using configuration software, the device to be selected is a PLC with Modicon (* Kang), Modbus RTU address type, integer 16 bit data, starting from 4001 using the Kingview register. Other configuration software may start from 3001.

Parameter code, parameter name, meaning

4x0001 PV measurement value (read-only)

4x0002 J1 J1 alarm status (readable and writable)

4x0003 J2 J2 alarm status (readable and writable)

4x0004 J3 J3 alarm status (readable and writable)

4x0005 J4 J4 alarm status (readable and writable)

Example: Read the PV (PV=1000) value of the instrument with address 1

Send data as 01 03 00 00 00 01 84 0A

The returned data is 01 03 02 03 E8 B8 FA (where 03 E8-1000), where 01 is the instrument address, 03 is the function number, 00 and 00 are the register start addresses, 00 and 01 represent reading a number, 84 and 0A are check codes, and B8 FA is the check code in the returned data. If you want to read PV and J1HA data, you can send: 01 03 00 00 02 C4 0B.

8Warranty

If it is a manufacturing quality problem caused by the factory, the instrument will be repaired free of charge from the date of leaving the factory. If the damage is caused by improper storage and use, the repair cost will be charged. The warranty period is twelve months, and the warranty period of 3-5 years must be specified separately.