Overview: The SD series universal soft start control cabinet is a single motor control device that uses intelligent soft starters as the main control components and is equipped with fast fuses, main circuit breakers, bypass contactors, and motor thermal relays. It can achieve multiple protections
※ Overview
The SD series universal soft start control cabinet is an intelligent typeSoft starterA single motor control device that integrates the main control components with fast fuses, main circuit breakers, bypass contactors, and motor thermal relays, and can achieve multiple protections.
※ Control function
The control device (with an optional all digital soft starter) is equipped with start and stop buttons, as well as operation, stop, and fault indicators. The device is equipped with remote control contacts, which include start and stop input contacts, operation indication output contacts, and fault output contacts (all passive relay contacts). It has functions of short circuit protection, overload protection, overheating protection, and phase failure protection.
|
※ Design selection
Starter model
|
rated current (A) |
Adaptive motor power (kW) |
Rated limit short circuit Current (KA) |
Adapt to fast melting Instrument specification (A) |
Optional external current Transformer specifications |
Standard load |
Heavy load |
SD017 |
17 |
7.5 |
5.5 |
50 |
50 |
75A/5A |
SD022 |
22 |
11 |
7.5 |
50 |
63 |
75A/5A |
SD032 |
32 |
15 |
11 |
50 |
100 |
75A/5A |
SD038 |
38 |
18.5 |
15 |
50 |
100 |
75A/5A |
SD047 |
47 |
22 |
18.5 |
50 |
125 |
75A/5A |
SD062 |
62 |
30 |
22 |
50 |
200 |
200A/5A |
SD075 |
75 |
37 |
30 |
50 |
200 |
200A/5A |
SD088 |
88 |
45 |
37 |
50 |
250 |
200A/5A |
SD110 |
110 |
55 |
45 |
50 |
315 |
200A/5A |
SD140 |
140 |
75 |
55 |
50 |
400 |
200A/5A |
SD170 |
170 |
90 |
75 |
50 |
400 |
500A/5A |
SD210 |
210 |
110 |
90 |
50 |
700 |
500A/5A |
SD250 |
250 |
132 |
110 |
50 |
700 |
500A/5A |
SD320 |
320 |
160 |
132 |
50 |
1000 |
500A/5A |
SD370 |
370 |
185 |
160 |
50 |
1000 |
500A/5A |
SD410 |
410 |
220 |
185 |
50 |
1250 |
1000A/5A |
SD480 |
480 |
250 |
220 |
50 |
1250 |
1000A/5A |
SD590 |
590 |
315 |
250 |
85 |
1800 |
1000A/5A |
SD660 |
660 |
355 |
315 |
85 |
1800 |
1000A/5A |
SD790 |
790 |
400 |
355 |
85 |
2500 |
1000A/5A |
technical indicators
meet the standard |
GB14048.6-1998,IEC947-4-2 |
Rated working voltage (Ue) |
AC380V, +15%, -20% |
Rated working current (Ie) |
17A ~ 790A, There are a total of 20 rated values, as shown in the selection comparison table |
Adapt motor power |
7.5kW ~ 400kW, Refer to the selection comparison table |
Usage category |
AC-53B control cage motor, short circuit (bypass) controller during operation |
Overcurrent characteristics |
3x current, withstand time 12s, cut-off time 600s |
rated frequency |
50±2Hz |
Rated working system S |
20 operation cycles per hour |
Design form |
Type 1 |
Rated insulation voltage (Ui) |
660V |
Rated impulse withstand voltage (Uimp) |
2500V |
Protection level |
IP20 |
pollution level |
3 |
Rated limit short-circuit current |
Refer to the selection comparison table |
Rated control power supply voltage Us |
AC220V, +20%, -30% |
Rated control power frequency |
50±2Hz |
Control power consumption |
≤5W |
Overvoltage detection |
+20% of rated operating voltage |
Undervoltage detection |
-35% of rated operating voltage |
Overcurrent detection |
4x to 15x (adjustable panel), continuous alarm for 0.1s |
overload protection |
Equivalent overload relay trip levels 10A, 10, 20, 30 (panel adjustable) |
Temperature over limit detection |
Heat sink temperature 60 ℃ |
communication interface |
RS-485 standard interface |
通信速率 |
Optional 2400bps, 4800bps, 9600bps, 19200bps |
ambient temperature |
Work: -20~+50 ℃,? Storage: -40~+70 ℃ |
ambient humidity |
≤ 95% without condensation or dripping |
working height |
No capacity reduction within an altitude of 1000m; The rated current decreases by 1%/100m above an altitude of 1000m |
cooling method |
Natural air cooling |
|