Overview

Features: (1) The low-temperature chiller unit adopts a twin-screw compressor, matched with an efficient condenser and evaporator

Product Details

1638442265212428 拷贝.jpg


Features:

(1) The low-temperature chiller unit adopts a twin-screw compressor, matched with an efficient condenser and evaporator.

(2) The unit is equipped with single and double circuit designs to meet customers' different choices. When a single compressor of the double circuit configuration unit fails, the other compressor can still operate normally without affecting its use.

(3) The screw type low-temperature chiller unit can be equipped with a remote management program to provide feedback on system operation information and achieve remote service.

(4) The unit can flexibly design the external dimensions according to the conditions of the computer room, and can be shipped in pieces and assembled on site.

(5) Screw type low-temperature chiller units are produced according to different power supply standards in different countries and regions. Screw water-cooled industrial integrated units and various high-voltage non-standard units can also be customized according to user requirements.


Unit classification:

1、 High temperature type: prepare a 0 ℃ frozen aqueous solution;

2、 Medium temperature: prepare a -5 ℃ frozen aqueous solution;

3、 Low temperature type: prepare a -10 ℃ frozen aqueous solution;

4、 Low temperature type: prepare a -15 ℃ frozen aqueous solution;

5、 Ultra low temperature type: prepare a -35 ℃ frozen aqueous solution;


Air cooled low-temperature freezer:

Widely used in industries such as plastics, electroplating, painting, electronics, fine chemicals, food, cultivation of shiitake mushrooms, grain and oil production, solar photovoltaic industry, air separation, automotive environmental testing chambers, engine intake systems/full room air conditioning, refrigeration, cold storage, etc.

Huaxiang air-cooled low-temperature freezer can control the temperature range from -40 ℃ to 30 ℃ And it can be adjusted freely. The compressor is made of French original grain wheel and Beijing Bizer, with sufficient cooling capacity and complete specifications, making it a new generation of refrigeration equipment.


Performance characteristics of air-cooled low-temperature freezer:

Adopting international brand specific low-temperature ****** high-efficiency scroll or piston compressors or screw compressors, with lower noise, smaller vibration, higher efficiency, better performance, lower failure rate, more reliability, energy saving and environmental protection.

The use of contactors, relays, thermal protectors, expansion valves, pressure controllers, and drying filters greatly improves the reliability of the entire machine.

Equipped with a high-efficiency copper tube finned condenser.

Compact structure, sufficient cooling capacity, high efficiency, easy to clean and maintain.

The unit is equipped with a stainless steel water tank and a high-performance, high flow dedicated water pump; Some models have two independent refrigeration systems that automatically adjust the number of systems involved in operation, achieving significant energy savings, and the systems can be used as backups for each other, resulting in higher reliability.

High precision digital controller, capable of intuitively and accurately measuring the temperature of cold water, with an accurate value of ± 0.1 ℃. The controller intuitively displays the operation and fault conditions of the compressor, water pump, and refrigeration system accurately;

Easy to operate, simply press the switch and the unit will automatically start running

Free provision of cooling and heating system solutions

Production oriented enterprises face equipment selection and system design issues when using chillers.
Huaxiang Refrigeration has been focusing on overall solutions for industrial refrigeration systems for 20 years, accumulating rich industry experience,
We provide you with a safe, energy-saving, easy to operate, and unmanned system solution

    1The selection of chiller units and supporting equipment is more reasonable, high-quality, and energy-saving

    2Application of self-control technology to achieve fully automatic operation, with simple and convenient operation

    3Based on the overall design scheme, the system runs more safely, reliably, and securely

    4IoT cloud service technology enables remote monitoring of mobile apps

    5The application of a large number of energy-saving technologies makes system operation more energy-efficient and economical

    6Provide SMS pre alert, collect and analyze energy consumption data for operation - selection

Product Parameters



Air cooled low temperature scroll chiller parameter sheet selection technical parameter table - air-cooled type
Model/Parameters refrigeration capacity

compressor

input power

chilled water

traffic

Freezing water pipe

caliber

cooling

air volume

cooling fan

power

refrigerant Overall dimensions
KW Kcal/hr KW m3/h m3/h KW Filling amount - kg L*W*H(mm)
HX-02FWD -5 3.4 2924 1.5 0.9 DN-32 2200.0 0.18*1 R404A-1.0kg 630*470*800
-10 2.6 2236 0.8
-15 1.8 1548 0.7
HX-03FWD -5 5.1 4386 2.2 1.5 3100.0 0.19*1 R404A-1.5kg 940*555*1060
-10 3.9 3354 1.3
-15 3.0 2580 1.2
HX-05FWD -5 9.5 8170 3.75*1 2.5 5400.0 0.19*2 R404A-3.0kg 1100*00*1350
-10 8.0 6880 2.3
-15 6.5 5590 2.0
HX-08FWD -5 15 13072 5.5*1 3.5 81000.0 0.52*2 R404A-4.5kg 1350*740*1430
-10 12 11008 3.3 DN-40
-15 10 8600 3.2
HX-10FWD -5 19 16340 3.75*2 4.8 11000.0 0.52*2 R404A-6.0kg 1450*780*1550
-10 16 13760 4.6
-15 13 11180 4.2
HX-12FWD -5 22 19608 4.2*2 5.8 12800.0 0.55*2 R404A-7.0kg 1510*780*1600
-10 19 16512 5.6
-15 15 13416 5.2
HX-15FWD -5 28 24510 5.5*2 7.0 15000.0 0.7*2 R404A-8.5kg 1600*890*1630
-10 24 20640 6.8
-15 18 15652 6.5
HX-20FWD -5 38 32680 7.5*2 9.6 DN-50 22000.0 0.78*2 R404A-11kg 1900*1000*1800
-10 32 2752 9.5
-15 26 22360 9.0
HX-25FWD -5 47 40850 10*2 11.8 DN-65 25000.0 0.7*3 R404A-12kg 2140*1000*1700
-10 40 34400 11.0
-15 32 27950 10.5
HX-30FWD -5 57 49020 7.5*3 14.0 31000.0 0.78*3 R404A-16kg 2400*1120*1900
-10 48 41280 13.0
-15 39 33540 12.0
HX-40FWD -5 76 65360 7.5*4 18.0 DN-80 42500.0 1.3*3 R404A-22kg 2200*1600*2000
-10 64 55040 17.0
-15 52 44720 16.0
HX-50FWD -5 95 81700 10*4 24.0 55000.0 1.3*4 R404A-27kg 2400*1600*2100
-10 80 68800 23.0
-15 65 55900 22.0
Note:
1. The cooling capacity is determined based on the following conditions: chilled water inlet temperature of 12 ℃, chilled water outlet temperature of 7 ℃, condenser air inlet temperature of 35 ℃, condenser air outlet temperature of 40 ℃;
2. When the operating temperature is below 5 ℃, please add antifreeze to prevent freezing. When the external ambient temperature is below 0 ℃ or the unit is not used for a long time, the accumulated water inside the machine should be drained to prevent copper pipes from freezing and swelling;
3. Chinese interface digital series control system for control system; Customized as a programmable PLC system, both capable of RS485 communication;
4. The design pressure of the chilled water side for standard models is 1.0Mpa; Container pressurization type (special order model) applicable design pressure:
5. The client has internal and external wire interfaces, and the flange mode is provided by the customer. The main power supply is 3-phase 380V 50Hz, and the operating power supply is single-phase 220V 50Hz; Please apply in advance when ordering non-standard power supplies;
6. For more detailed parameters, please contact your Huaxiang distributor.

Learn more parameters or click to consult