IIRequest for functionality and technical specifications
●4~20mAIndustrial standard signal input, provided in the table24VFeed, on-site probes do not require additional power supply. |
3、 Terminal wiring

4、 Operating instructions
(1) Key function
■— During the setting process, press once to return to the previous setting operation, and hold down for more than2Exit the set state in seconds.
EnWhen setting the state, it is used to store the new set value of the parameter and enter the next parameter setting
▲ - Used to increase the set value when setting the state.
▼- Used to reduce the set value when setting the state.
In the set state, if pressed▲ orPress the ▼ key and the value will quickly increase or decrease. Release it and stop.
(2) Power on self-test
⑴ Connect the power supply, input, output, alarm and other wiring of the instrument according to the wiring diagram of the instrument.
Carefully check the wiring of the instrument, and only connect the power after it is correct.
⑶Instrument display after power onHELO,PASSIndicates that the instrument self-test has passed,If displayed-HH-Indicating over limit or broken couple and thermal resistance open circuit,The instrument adopts a human-machine dialogue form to input parameters,Use various prompts to indicate the data that should be entered.
(3) Parameter setting
(4)appear-LP-Please enter the number of channels for the instrument,Scope from1-4The factory value is set to4Indicating that the instrument is4Channel input instrument.
Input signal selection comparison table:
instrument prompttalisman |
Input signal content |
instrument prompttalisman |
Input signal content |
P100 |
Pt100 |
tc-t |
Ttype |
C100 |
Cu100 |
tc-n |
Ntype |
Cu50 |
Cu50 |
tc-J |
Jtype |
bA1 |
bA1 |
4-20 |
4-20mA |
bA2 |
bA2 |
0-10 |
0-10mA |
Tc-s |
Stype |
0-20 |
0-20mA |
Tc-k |
Ktype |
1-5U |
1-5V |
Tc-e |
Etype |
0-5U |
0-5V |
Tc-b |
Btype |
0-50 |
0-50mV |
(7) 1dot- * Channel decimal point position, range0~3, such asdot=2, the display format isXX. XX.For temperature signals such as thermistor and thermocouple, the large setting is1The display resolution is0.1℃, in1000Automatic conversion above degreeresolutionfor1℃.
(8) 1-PLThe lower limit of the linear input of the channel corresponds to the displayed value, which is the lower limit of the sensor range-1999~9999.
(9) 1-PHThe upper limit of the linear input of the channel corresponds to the displayed value, which is the upper limit of the sensor range-1999~9999.
Set the input parameters for the second to fourth channels in sequence.
(12) 1-HAChannel relay upper limit alarm set value.
(13) 1-HHChannel relay shutdown setting value.
Set the reports for the second to fourth channels in sequencejingMethod and set values.
(14)1-EoChannel zero point error correction coefficient.
Set the error correction for the second to fourth channels in sequence.
(15) Addr- Communication address refers to the instrument number and range1~99.
(16) bAUd- Communication baud rate, range1200~9600.
Parameter settings completed and displayed-EndExit the setting state and enter the running state.
5、 Warranty
If it is a manufacturing quality problem caused by the factory, the instrument will be repaired free of charge from the date of leaving the factory. If the damage is caused by improper storage and use, the repair cost will be charged. The warranty period is 18 months, and the warranty period of 3-5 years must be specified separately. Ordinary instruments can be returned within 15 days and replaced within 30 days.