User Manual for Digital AC Ammeter AOB184I-9K1
I. Overview
The digital display AC ammeter AOB184I-9K1 is a new generation of economical digital installation type electric meter, mainly used for real-time measurement and indication of AC current in electrical circuits. It has the characteristics of high measurement accuracy, good stability, long-term operation without calibration, and can set parameters on site through panel buttons. It is an ideal replacement product for the original pointer instrument or ordinary digital instrument.
Adopting SMT production technology, the circuit is simple and highly reliable;
Communication sampling is a method of measuring the root mean square value;
Programmable instrument range setting;
It can have the function of over limit alarm output, with programmable settings for alarm upper and lower limits, switching difference, output delay time, and power on alarm suppression;
*The installation method can be easily completed without the need for tools;
The performance of smart watches and the price of regular watches.
3、 Technical parameters of digital AC ammeter AOB184I-9K1
Range (sustainable overload 1.2 times)
Direct measurement with AC voltmeter: AC 0-100V, AC 0-500V External voltage transformer: AC */100V
Direct measurement with DC voltmeter: DC 0 to ± 500V
Direct measurement with AC ammeter: AC 0-1A, AC 0-5A External current transformer: AC */1A, AC */5A
Direct measurement with DC ammeter: DC 0~± 5A External shunt: DC */75mV
Accuracy: ± 0.5% of the instrument range
Sampling rate: AC 1 time/second, DC 2 times/second
Frequency range of communication input signal: 45~65Hz
Input circuit power consumption:<0.5VA
Auxiliary power supply: AC 220V ± 10% 50/60Hz
Auxiliary power consumption:<3VA
Overflow indication: Positive overflow displays "HHHH", negative overflow displays "LLLL"
Alarm output: Same relay output for upper and lower limit alarms, contact capacity AC 250V/1A, DC 30V/1A, resistive load
Working environment: Non corrosive environment with temperature ranging from -10 to 50 ℃ and humidity ≤ 85% RH