*Frequency modulation series resonance test device

NegotiableUpdate on 01/21
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The frequency modulation series resonance test device utilizes this technology to design and manufacture the XUJIXZB series frequency modulation series resonance test device, which adopts 16 bit fine frequency conversion, 10KHz carrier frequency, SPWM, and imported original IPM integrated module. It meets the regulations and requirements for high-voltage experiments.

Product Details

XUJIXZB-240KVA/60KV Frequency Modulation Series Resonance Test DeviceDetailed Introduction

This catalog is carefully selected by Shanghai Xuji Electric Co., Ltd. for you:

Frequency modulation series resonance test deviceDetailed information:

Introduction

Shanghai Xuji Electric Co., LtdFrequency modulation series resonance test deviceThe independently developed frequency conversion and voltage regulation software technology in the field is used in the domestic high-voltage testing industry, utilizing 16 bit precision frequency conversion, 10KHz carrier frequency, SPWM, and imported original IPM overall module design and manufacturingFrequency modulation series resonance test deviceComply with the regulations and requirements for high-voltage experiments.
The frequency conversion series resonance test device is widely used in industries such as power, metallurgy, petroleum, chemical, etc. It is suitable for high-capacity and high-voltage capacitive test samples, such as generators, transformers, etc GIS、 Handover and preventive tests for high-voltage cross-linked cables, transformers, bushings, etc.

Frequency modulation series resonance test deviceworking principle
Frequency modulation series resonance test deviceUsing the principle of series parallel resonance, by adjusting the output frequency of the variable frequency controller, the inductance L of the reactor in the circuit and the capacitance C of the test sample resonate, and the resonant voltage is the voltage applied to the test sample. The power supply is provided through the frequency modulation controller, and the test voltage is initially boosted by the excitation transformer to apply high voltage to the reactor L and the test sample CX. By changing the output frequency of the frequency modulation controller, the circuit is in series resonance state; The resonant frequency of the circuit depends on the capacitance CX of the test sample and the inductance L of the reactor. Adjust the output voltage of the variable frequency controller to achieve the required voltage value of the high voltage on the test sample.

Frequency modulation series resonance test deviceProduct Features
The large screen displays test data and test status, and has real-time operation step prompt function
Can flexibly adjust the experimental voltage, frequency range, and pressurization time
The test results can calculate the capacitance of the test sample
Equipped with computer communication interface for easy communication and management of experimental data
Small size, light weight, easy operation
High resolution, frequency resolution of 0.001HZ
High safety and reliability, the system has overcurrent, overvoltage, and discharge protection functions, which can effectively protect personal and equipment safety. The test results can be printed and upgraded with software

Frequency modulation series resonance test deviceComplete set composition
The complete set of equipment consists of a variable frequency voltage regulating power supply, excitation transformer, reactor, voltage divider, and compensation capacitor.

Frequency modulation series resonance test deviceTechnical Specifications
Environmental temperature: -10~45 ℃
Environmental humidity: ≤ 90%
Altitude: ≤ 2000M
Power input: 220V ± 10% single-phase 50Hz output 0-2220V (≤ 10KW)
380V ± 10% three-phase 50Hz output 0-400V
Rated test capacity: 0-8000KVA (optional) Instability: ≤ 0.05%
Resonant voltage: 0-1000KV (optional) Output waveform: sine wave
Frequency adjustment range: 0.1-300Hz, waveform distortion rate: ≤ 0.5%
System measurement accuracy: 0.5 level noise: ≤ 60dB
Frequency regulation Frequency division rate: 0.01Hz Reactor Q value: 30-200 (optional)