Structural principle of vibrating rod level controller
Vibration rod level controllerComposed of vibration rod components and electronic circuit components. The instrument uses the "resonance" principle of a tuning fork. The vibrating rod and the built-in vibrating rod form a "tuning fork" resonance probe with a frequency of 280Hz. Under the drive of piezoelectric elements, vibration occurs. When the probe touches the measured material, the vibration amplitude sharply decreases, which is converted into an electronic signal, causing the relay to switch on and off.
Technical parameters of vibrating rod level controller
Power supply: 220V/105V AC50/60Hz
Power consumption: 2VA
Vibration frequency: 280Hz
Work pressure: 2MPa
Working temperature: Probe section: -30~150 ℃
Electronic part: -30~70 ℃
Probe length: SVD-210 standard type: 189mm
SVK-220 Extended Type: 250~5000mm
Contact capacity: 250V 10A AC, 30V 5A DC
Delay time: measured (from vibration to stop): 0.5S
Restoration (from stop to vibration): 1 second
Switch function: normally open NO or normally closed NC
Material: Probe: OCr18Ni9 (304)
Control box: ADC (surface spray coating)
Installation type: Thread: 3/2 'NPT, R3/2' (PT3/2)
Flange: DN25, PN1.0 or PN2.5, convex surface
Model and specifications of vibrating rod level controller
| Svk- 200 | Vibration rod level switch | ||||
|
| 210 | Standard type, probe length: 189mm | Probe form | ||
|
| 220 | Extended type, probe length: 250~5000mm | |||
|
|
| A | Threaded installation, 3/2 "NPT | Installation type | |
|
|
| B | Threaded installation, R3/2" (PT3/2) | ||
|
|
| C | Flange installation, DN25,PN1.0MPa,RF | ||
|
|
| D | Flange installation, DN25,PN2.5MPa,RF | ||
|
|
|
| -□□□□ | Extended probe length, in millimeters | Extended measuring rod length |
Typical Applications
Liquids: petroleum, various fuels, acids, alcohol, various beverages, beer, liquefied gas, pure water, etc;
Mixed liquids: factory waste liquid, urban drainage, pesticides, industrial products, various aqueous solutions;
Interface: Crude oil and water, mercury in water, precipitates in alcohol and acidic water, etc
Instant noodles: beer foam, soap foam, etc;
Viscous body: various coatings, binders, resins, detergents, molasses, various pulp grades, slurries, etc;
Powder: cement, lime, iron powder, fertilizer, laundry detergent, refined salt, refined sugar, flour, milk powder, etc;
Particles: chemical raw materials, pharmaceuticals, food, etc;
Blocks: coal blocks, limestone, ores, etc.
Precautions for installation and use of vibrating rod level controller
1. Installation should be avoided at the inlet;
When installing in blocks with a particle diameter greater than 15mm or less than 7 meters below the feeding port, a probe cover should be added;
When measuring powders with high viscosity, they should be installed vertically from the top of the container or inserted diagonally from the side wall.
When the temperature of the probe exceeds 120 ℃, due to the shortened lifespan of the piezoelectric element, it is necessary to regularly check whether the switch action is normal.