Schneider EOCR-DG Electric Motor Leakage Protector China General Agent
EOCR-DG Product Introduction:
EOCR-DG is a motor protector product from Schneider EOCR, which has protection functions such as leakage, overcurrent, phase loss, reverse phase, locked rotor, and current imbalance.
EOCR Introduction:
EOCR stands for Electronic Over Current Relays, an abbreviation for Electronic Motor Protection Relays. Sanhe EOCR Co., Ltd. is a major motor protector manufacturer in South Korea, founded by Dr. Kim In sik in 1981 and headquartered in Seoul, South Korea. In 2001, in order to develop the company into a strategic enterprise, it subsequently joined Schneider Electric Group in France and was renamed Schneider Electric Korea Ltd in 2009. The product has also been renamed Schneider EOCR motor protector.
EOCR-DG product performance:
√ Built in MCU (Micro Processing Controller)
√ Overcurrent/phase loss/reverse phase/imbalance/locked rotor/grounding protection
√ Grounding protection for residual current detection method
√ Wide current setting range
√ Automatic calculation of startup delay time
√ Display operation and reason for operation
√ Fixed time operation characteristics
√ Manual (immediate) reset/automatic (remote) reset function
√ * Environmental Applicability
√ Ultra low power consumption
√ No voltage release function (power-off protection function/fail safe operation) - N type
√ DG: through type DGT: terminal type
Schneider EOCR-DG Electric Motor Leakage Protector China General AgentEOCR-DG Technical Parameters:
protection function |
Protection action time |
overcurrent |
O-Time |
phase loss |
Within 4 seconds |
locked-rotor |
D-Time 后 I>Is*3 |
unbalanced |
8 seconds |
grounding |
0.5 seconds |
reverse |
0.1 seconds |
Current setting |
Specifications |
Current setting range |
Grounding current setting range |
|||
|
05 |
0.5~6A |
0.5~2A |
|||
|
30 |
3.0~30A |
1~5A |
|||
|
30~600 |
05 type combined with external CT |
0.5~2A |
|||
time |
Startup time |
D-Time |
Automatic calculation (up to 60 seconds) |
|||
|
Action Time |
O-Time |
0.2~15 seconds |
|||
Reset method |
Manual (instant)/electric (remote) reset |
|||||
Run time characteristic curve |
time limit |
|||||
Operation Display |
5 LED |
|||||
error |
current |
±10% |
||||
|
time |
±10% |
||||
power control |
voltage |
110 |
AC85~150V |
Other AC/DC 24V |
||
|
|
220 |
AC180~260V |
|||
|
frequency |
50/60HZ |
||||
Auxiliary contact |
Output contact |
2-SPST(1a1b) |
||||
|
state |
R型 |
Normal state (after providing power: 95-96 closed point, 97-98 open point) |
|||
|
|
N-type |
Normal state (after power supply: 95-96 open point, 97-98 closed point) |
|||
|
capacity |
AC250V/3A resistive |
||||
insulation |
insulation resistance |
Between the shell and the circuit |
100M Ω or higher than megohmmeter DC500V |
|||
|
compressive strength |
Between the shell and the circuit |
2.0KV,50/60HZ,1min |
|||
|
|
Between output contacts |
1.0KV,50/60HZ,1min |
|||
|
|
Between lines |
2.0KV,50/60HZ,1min |
|||
Usage environment |
temperature |
storage |
-30~+80℃ |
|||
|
|
run |
-20~+60℃ |
|||
|
humidity |
30-85% RH without condensation |
||||
install |
35mm DIN rail/fixed |
|||||
EOCR-DG wiring diagram:

EOCR-DG product size diagram:

EOCR-DG selection table:

EOCR-DG specialized current transformer: