TQSW Power Frequency Non Partial Discharge Test Transformer
I. Overview
In order to adapt to different voltage levels and capacities of power equipment for power frequency voltage testing, our company manufactures various specifications ofTQSW series power frequency non partial discharge test transformerUsers can choose according to their own needs.
TQSW series power frequency test transformerIt is divided into iron shell type and insulation cylinder type, which are respectively single-stage and series type. The iron shell type is suitable for situations with low local discharge requirements, the insulated cylinder type is suitable for situations with high local discharge requirements, the single-stage type is suitable for situations with low voltage and large capacity, and the series type is suitable for situations with high or low voltage, small capacity, and easy portability.
2、 Product Model Compilation Instructions
This model is compiled in accordance with JB/T.3837<<Method for Model Compilation of Transformer Products>>
3、 Usage conditions
1. Altitude not exceeding 1000 meters
2. The ambient air temperature is -5 to+40 ℃, and the relative humidity of the air is not more than 85% (+20 ℃). When changing from one environment to another, the temperature difference should not exceed 15K.
3. No conductive dust exists
4. No fire or explosive hazardous materials
5. There is no gas present that corrodes metals and insulation
6. Places without severe vibrations and collisions
7. The unevenness of the ground shall not exceed 3 degrees
8. The waveform of the power supply voltage is a sine wave with a distortion rate of less than 3% and a frequency of 50Hz. The power supply side should not be subjected to external atmospheric overvoltage.
9. There is a reliable grounding point with a grounding resistance of less than 0.5 Ω
4、 Technical parameters
1. Partial discharge capacity (insulated cylinder type)
A. 10-200KV rated voltage (U)H)At 100% UH, the local discharge capacity is ≤ 3-5 Pc
B. 250-300KV rated voltage (U)H)Under 100% UH, the local discharge capacity is ≤ 5Pc
C. 350-750KV rated voltage (UH)Partial discharge capacity ≤ 5Pc at 80% UH and ≤ 10Pc at 100% UH
D. 800KV~1500KV rated voltage (UH)At 80% UH, the local discharge capacity is ≤ 10Pc
2. Cascade test transformer, uneven voltage distribution between two or three sections ≤ 5%
3. Allowable operating time: The test transformer can run for 30 minutes from ambient temperature at rated voltage and current, and can run continuously at two-thirds of the rated voltage and current
4. The impedance of a single test transformer is 3% to 12%, and the impedance of a series connection is 5% to 25%
5. Waveform distortion rate<3%
6. The remaining parameters comply with the provisions of JB/T9641-1999<<Test Transformer>>
| Model | Rated capacity (kVA) | High voltage (kV) | Low voltage (kV) | D × H(mm) | Weight (kg) |
| -5/50 | 5 | 50 | 0.22 | 320 × 431 | 45 |
| 10/100 | 10 | 100 | 0.22 | 570 × 725 | 165 |
| 30/100 | 30 | 100 | 0.38 | 800 × 1036 | 315 |
| 15/150 | 15 | 150 | 0.38 | 1165 × 1667 | 695 |
| 50/250 | 50 | 250 | 0.38 | 1280 × 1970 | 1100 |
| 100/100 | 100 | 100 | 0.38 | 1130 × 1485 | 1350 |
| 100/150 | 100 | 150 | 0.38 | 1800 × 1953 | 1980 |
| 200/200 | 200 | 200 | 0.6 | 2500 × 2445 | 4500 |
| 150/250 | 150 | 250 | 0.6 | 2150 × 2443 | 4230 |
| 250/250 | 250 | 250 | 0.6 | 2500 × 2555 | 6100 |
| 1000/250 | 1000 | 250 | 3. 6, 10 | 3600 × 2800 | 12000 |
| 300/300 | 300 | 300 | 3. 6 | 2600 × 3300 | 6280 |
| 450/300 | 450 | 300 | 3. 6 | 3050 × 2920 | 8000 |
| 600/300 | 600 | 300 | 3. 6 | 2600 × 3460 | 10600 |
| 800/400 | 800 | 400 | 3. 6, 10 | 3600 × 4800 | 14000 |
| 1200/400 | 1200 | 400 | 3. 6, 10 | 3600 × 4875 | 19000 |
| 100/500 | 100 | 500 | 3. 6, 10 | 3300 × 5300 | 8100 |
| 250/500 | 250 | 500 | 3. 6, 10 | 3600 × 5200 | 11600 |
| 200/500 | 200 | 500 | 3. 6, 10 | 3300 × 5300 | 8800 |
| 500/500 | 500 | 500 | 3. 6, 10 | 3600 × 5210 | 23540 |
| 1000/500 | 1000 | 500 | 3. 6, 10 | 3600 × 5300 | 25400 |
| 2200/550 | 2200 | 550 | 6. 10 | 3600 × 6000 | 36000 |
| 2000/500 | 2000 | 500 | 6. 10 | 3600 × 5400 | 34880 |
Product nickname: Non partial discharge high voltage test transformer, Non partial discharge power frequency withstand voltage test device, Non partial discharge test transformer complete set device, Non partial discharge power frequency test transformer, Non partial discharge test transformer complete set test equipment, Non partial discharge power frequency test transformer, Non partial discharge transformer, Non corona gas filled test transformer, Non partial discharge test system, Non partial discharge ultra light high voltage test transformer, Non partial discharge gas filled transformer, Power frequency Non partial discharge test transformer, Partial discharge test transformer, Partial discharge test equipment