PUL61.XXBXXHKMXX radar level gauge PS61

Product Details

PULS61.XXBXXHKMXX radar level gauge VEGAPULS61

Radar Level Gauge/Radar Level Gauge (VEGAPULS 61)

■ Measurement principle:

Transmit and receive extremely short microwave pulses with low energy through an antenna. Radar waves travel at the speed of light. The VEGAPULS radar level gauge/level gauge/level gauge imported from Germany accurately analyzes the level echo through new microprocessing technology and unique ECHOFOX software, measures the running time of radar waves accurately, and converts them into level signals through electronic components, ensuring stable and precise measurement of material or liquid position in a very short time. By inputting the container size, the distance value above can be converted into a signal proportional to the level, and the level gauge can be adjusted for empty storage.

■ advantage

-Maintenance free, non-contact measurement.

-Due to its wear resistance and maintenance free nature, the equipment has a wide range of applicability.

-Accurate and reliable measurement.

■ application

  VEGAPULS 61 is used to measure liquid levels. It is particularly suitable for liquid level measurement and monitoring under simple process conditions. VEGAPULS 61 is economical and practical, with simple and flexible installation. The encapsulated antenna ensures permanent maintenance free operation.

Main performance parameters

scope of application Liquid
Measuring distance 35 meters
measurement accuracy ± 2 millimeters
Ambient Temperature -40~+80℃
Work environment pressure -1~+3bar (-100~+300 kPa)

■ Selection Guide

Security certification:
XX
┄
┄
┄
┄
┄
┄
┄
┄
No explosion-proof requirements
XM
┄
┄
┄
┄
┄
┄
┄
┄
Marine license
CX
┄
┄
┄
┄
┄
┄
┄
┄
ATEX II 1G, 1/2G, 2G Ex ia IIC T6
CA
┄
┄
┄
┄
┄
┄
┄
┄
ATEX II 1G, 1/2G, 2G Ex ia IIC T6 + WHG
CM
┄
┄
┄
┄
┄
┄
┄
┄
ATEX II 1G, 1/2G, 2G Ex ia IIC T6+Marine License
CI
┄
┄
┄
┄
┄
┄
┄
┄
IEC Ex ia IIC T6
DX
┄
┄
┄
┄
┄
┄
┄
┄
ATEX II 1/2G, 2G Ex d ia IIC T5/T6
DI
┄
┄
┄
┄
┄
┄
┄
┄
IEC Ex d ia IIC T6
│
Version/Material/Operating Temperature:
│
A
┄
┄
┄
┄
┄
┄
┄
Sealed horn antenna ø 40mm/PVDF/-40~80 ° C
│
B
┄
┄
┄
┄
┄
┄
┄
Plastic horn antenna ø 80mm/PP/-40~80 ° C
│
│
Installation connection/materials:
│
│
XX
┄
┄
┄
┄
┄
┄
No installation flange
│
│
GP
┄
┄
┄
┄
┄
┄
Thread G1 1/2 (DIN3852-A) PN3 / PVDF
│
│
NP
┄
┄
┄
┄
┄
┄
Thread 1 1/2NPT (ASME B1.20.1)PN3 / PVDF
│
│
XG
┄
┄
┄
┄
┄
┄
Countersunk nut G1 1/2 / PPH
│
│
CA
┄
┄
┄
┄
┄
┄
Clamp 2 "PN3 (ø 64mm) DIN32676, ISO2852/316L
│
│
CB
┄
┄
┄
┄
┄
┄
Clamp 3 "PN3 (ø 91mm) DIN32676, ISO2852/316L
│
│
RA
┄
┄
┄
┄
┄
┄
Bolt DN50 PN3, DIN 11851/316L
│
│
RB
┄
┄
┄
┄
┄
┄
Bolt DN80 PN3, DIN 11851/316L
│
│
XC
┄
┄
┄
┄
┄
┄
Installation ring 170mm/316L
│
│
XD
┄
┄
┄
┄
┄
┄
Installation ring 300mm/316L
│
│
YD
┄
┄
┄
┄
┄
┄
Combi compr.flange DN80PN16, ANSI3"150lb / PPH
│
│
AE
┄
┄
┄
┄
┄
┄
Flange DN100PN16 FKM (Viton)/PPH
│
│
AH
┄
┄
┄
┄
┄
┄
Flange DN150PN16 FKM (Viton)/PPH
│
│
FK
┄
┄
┄
┄
┄
┄
Flange ANSI 4 "150psi FKM (Viton)/PPH
│
│
FM
┄
┄
┄
┄
┄
┄
Flange ANSI 6 "150psi FKM (Viton)/PPH
│
│
UC
┄
┄
┄
┄
┄
┄
Flange JIS DN100 10K FKM (Viton)/PPH
│
│
UE
┄
┄
┄
┄
┄
┄
Flange JIS DN150 10K FKM (Viton)/PPH
│
│
│
Output interface:
│
│
│
H
┄
┄
┄
┄
┄
2-wire system 4-20mA/HART ®
│
│
│
1
┄
┄
┄
┄
┄
2-wire system 4-20mA/HART ® And PLICSMOBILE
│
│
│
B
┄
┄
┄
┄
┄
Four wire system 4... 20mA/HART ®; 90...253V AC; 50/60Hz
│
│
│
I
┄
┄
┄
┄
┄
Four wire system 4... 20mA/HART ®; 9.6...48V DC; 20...42V AC
│
│
│
P
┄
┄
┄
┄
┄
Profibus PA
│
│
│
F
┄
┄
┄
┄
┄
Foundation Fieldbus
│
│
│
│
Shell/Protection Level:
│
│
│
│
K
┄
┄
┄
┄
Plastic casing/IP66/IP67
│
│
│
│
A
┄
┄
┄
┄
Aluminum casing/IP66/IP68 (0.2 bar)
│
│
│
│
D
┄
┄
┄
┄
Aluminum shell double chamber/IP66/IP68 (0.2 bar)
│
│
│
│
8
┄
┄
┄
┄
Stainless steel (electrolytic polishing) 316L/IP66/IP68 (0.2 bar)
│
│
│
│
W
┄
┄
┄
┄
Stainless steel double chamber/IP66/IP68 (0.2 bar)
│
│
│
│
R
┄
┄
┄
┄
Plastic dual chamber/IP66/IP67
│
│
│
│
│
Connecting cables/cable sealing covers/connecting plugs:
│
│
│
│
│
M
┄
┄
┄
M20x1.5/Yes/No
│
│
│
│
│
N
┄
┄
┄
1/2NPT/None/None
│
│
│
│
│
│
Display Debugging Module (PLICSCOM):
│
│
│
│
│
│
X
┄
┄
not have
│
│
│
│
│
│
A
┄
┄
Top installation
│
│
│
│
│
│
│
X
┄
Additional equipment: None
↓
↓
↓
↓
↓
↓
↓
↓
PS61.
##
#
##
#
#
#
#
X
: Select model