E-mail
2852533474@qq.com
-
Phone
13611660940
-
Address
Room 1216, No. 4, Lane 680, Shuishe West Road, Baoshan District, Shanghai
Shanghai Jijin Automation Equipment Co., Ltd
2852533474@qq.com
13611660940
Room 1216, No. 4, Lane 680, Shuishe West Road, Baoshan District, Shanghai
MINI MCR-2-UNI-UI-2UI signal multiplier
A four terminal amplifier that can be configured universally, using switch output and plug-in connection technology, used to double analog signals. Configure through DIP switches or software. Screw connection technology, standard configuration.
| width | 6.2 mm |
|---|---|
| height | 110.5 mm |
| depth | 120.5 mm |
Back to top
| Environmental temperature (operating) | -40 °C . .. 70 °C |
|---|---|
| Environmental temperature (storage/transportation) | -40 °C . .. 85 °C |
| Allow humidity (operation) | 5 % . 95% (no condensation) |
| Anti noise | When EN 61000-6-2 is disturbed, it may be a small deviation. |
Back to top
| Input quantity | 1 |
|---|---|
| Configurable/Programmable | yes |
| Voltage input signal | 0 V... 10 V (via DIP switch) |
| 2 V... 10 V (via DIP switch) | |
| 0 V... 5 V (via DIP switch) | |
| 1 V... 5 V (via DIP switch) | |
| 0 V... 12 V (can be set through software) | |
| Current input signal | 0 mA... 20 mA (via DIP switch) |
| 4 mA... 20 mA (via DIP switch) | |
| 0 mA... 10 mA (via DIP switch) | |
| 20 mA... 0 mA (via DIP switch) | |
| 0 mA... 24 mA (can be set through software) | |
| Large input voltage | 12 V |
| Large input current | 24 mA |
| Input resistance of input voltage | > 120 kΩ |
| Input resistance of input current | Approximately 50 Ω (+0.7 V for testing diodes) |
Back to top
| Output quantity | 2 |
|---|---|
| Voltage output signal | 0 V... 10 V (via DIP switch) |
| 2 V... 10 V (via DIP switch) | |
| 0 V... 5 V (via DIP switch) | |
| 1 V... 5 V (via DIP switch) | |
| 0 V... 10.5 V (can be set through software) | |
| Current output signal | 0 mA... 20 mA (via DIP switch) |
| 4 mA... 20 mA (via DIP switch) | |
| 0 mA... 10 mA (via DIP switch) | |
| 20 mA... 0 mA (via DIP switch) | |
| 0 mA... 21 mA (can be set through software) | |
| High output voltage | Approximately 12.3 V |
| High output current | 24.6 mA |
| short-circuit current | ≤ 25 mA |
| Load/Output Load Voltage Output | ≥ 10 kΩ |
| Load/Output Load Current Output | ≤ 600 Ω (per channel) |
| fluctuation | < 20 mVSS(At 600 Ω) |
| < 20 mVSS(At 600 Ω) |
MINI MCR-2-UNI-UI-2UI signal multiplier
A four terminal amplifier that can be configured universally, using switch output and plug-in connection technology, used to double analog signals. Configure through DIP switches or software. Screw connection technology, standard configuration.
| Electromagnetic Compatibility | Compliant with EMC regulations |
|---|---|
| Emission interference | EN 61000-6-4 |
| Standards/regulations | EN 61000-4-2 |
| name | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| name | Conducted interference |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | Strengthen insulation in accordance with IEC 61010-1 standard requirements |
| compliance | Compliant with CE standards |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| DNV GL - Temperature | B |
| DNV GL - Humidity | B |
| DNV GL - Vibration | A |
| DNV GL-EMC | A |
| DNV GL - Shell | Required protection according to the Rules shall be provided upon installation on board |
| Fire protection of railway vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection of railway vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection of railway vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Back to top
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmental protection usage period=50 |
| For more details on harmful substances, please refer to the "Manufacturer's Statement" in the "Download Area" |