Measurement principle: Fuel cell display mode: 128 × 64 dot matrix LCD measurement range: 0~10/100/1000ppm, 0~25
Measurement principle: fuel cell
Display mode: 128 × 64 dot matrix LCD
Measurement range: 0~10/100/1000ppm, 0~25.00% O2
(Available in different ranges: trace or constant)
Measurement accuracy: 0~1000ppm/1.00%/10.00%/25.00%≤±1%FS
0~100ppm≤±2%FS
0~10ppm≤±5%FS
Repeatability:≤±1%
Response time: T90 ≤60S
Analog output: 4~20mA.DC (non isolated output, load resistance less than 500 ohms)
1 programmable dry contact type passive alarm output, contact * * capacity 220VAC/2A
Power supply: DC24V/0**
Sample gas temperature: 0~50 ℃
Environmental humidity:<80% RH
Sampling method: through type
Sample gas flow rate: 600~800ml/min
Inlet pressure: 90~110KPa, pressure stabilizing atmosphere (* * pressure)
Sample gas composition: no strong corrosive gas, dust content less than 1mg/Nm3
Specifications and dimensions: 196mm × 170mm × 134mm (H × W × D)
Service life:>24 months (under normal usage conditions)
Explosion proof grade: Exd IIB T4
Installation method: Wall mounted