Welcome Customer !

Membership

Help

Hebei Puxindun Instrument Co., Ltd
Custom manufacturer

Main Products:

mechb2b>Products

Dewell 605-60pa Micro Differential Pressure Transmitter

NegotiableUpdate on 01/23
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

Dewell 605-60pa micro differential pressure transmitter can indicate the micro differential pressure of air or other compatible gases on site, and can also transmit output signals. This multifunctional instrument is more suitable for heating, ventilation, and air conditioning systems, especially in situations where on-site inspection, maintenance, and fault analysis are required. It has clear on-site readings and is powered by a two-wire circuit,

Product Details

Dewell 605-60pa Micro Differential Pressure Transmitter

Applications and Cases

Monitor duct pressure and indoor building pressure

Filter status monitoring

Clean room pressure on-site indication and remote signal transmission to control room

Technical indicators of indicator table
Medium air and non combustible, compatible with gases;
Please consult the factory for materials;Accuracy is shown in the model table;Stability at full scale ± 1% per year;The withstand voltage range is shown in the model table;Temperature range 20 to 120 ° F (-6.67 to 48.9 ° C);

Process connection 1/8 '' NPT internal thread;Size 4 '' (101.6 mm) dial, 5 '' (127 mm) outer diameter x 2-11/16 '' (68.3 mm);Weight 1 lb, 12.6 oz (811 g);Certification CE

605 series Dwyer with indication micro differential pressure transmitter
Technical specifications of transmitter
Accuracy is shown in the model table (including linearity, hysteresis, repeatability)

Temperature range 20 to 120 ° F (-6.67 to 48.9 ° C)

Compensation temperature range 32 to 120 ° F (0 to 48.9 ° C)

Temperature affects the full scale by ± 0.025%/° F (0.045% FS/° C)

Power supply 10-35 VDC (2-wire)

Output signal 4 to 20 mA

Zero and range adjustment potentiometer with protection

Loop resistance DC; large 0-1250 Ω

Current consumption DC; up to 38 mA

Electrical connection screw terminal block

The installation position of the diaphragm is vertical. If it is installed in other directions, please consult the factory