The main functions of SX-3050 equipotential connection resistance tester are:
Function |
Testing of equipotential bonding resistance between metal components, low value resistance testing, resistance testing of connecting conductors between ground grid electrodes, contact resistance testing, etc |
DC resistance range |
0.0001Ω~30.00KΩ 精度 ±1%rdg±5dgt |
Resistance resolution |
0.0001Ω |
detection method |
Four line method test |
test current |
≥1A |
open-circuit voltage |
≤7V |
Power |
Measurement power ≤ 15W |
DC voltage range |
0.0V~1000V DC accuracy ± 1.5% rdg ± 5dgt |
DC voltage resolution |
0.1V |
AC voltage range |
0.0V~750V AC accuracy ± 1.5% rdg ± 3dgt |
AC voltage resolution |
0.1V |
power supply |
DC 6V 4. h high-capacity battery with continuous standby time of over 100 hours |
Backlight |
Controllable gray and white screen backlight, suitable for use in dark fields |
display mode |
4-digit ultra large LCD display, gray and white screen backlight |
Measurement indication |
LED flashing indication during measurement, LCD countdown display |
LCD size |
108mm×65mm |
Instrument size |
Length, width, and height: 277.2mm × 227.5mm × 153mm |
Test line length |
2 pieces of red 5m and 2 pieces of black 5m each |
measure time |
Resistance test: about 3 seconds/time; Voltage test: approximately 2 times per second |
USB port |
Equipped with USB interface, software monitoring, data storage for uploading to computer, saving and printing |
Communication line |
1 USB communication cable |
data storage |
500 sets, "MEM" storage indicator, displaying the "FULL" symbol to indicate that the storage is full |
Data retrieval |
Data retrieval function: "MR" symbol display |
Overflow display |
Overscale overflow function: "OL" symbol display |
alarm function |
When the measured value exceeds the alarm set value, an alarm prompt will be issued |
battery voltage |
Real time display of battery level, reminding timely charging when battery voltage is low |
Auto Shutdown |
APO "indicates that it will automatically shut down after 15 minutes of startup |
power waste |
Standby: 30mA Max (backlight off) |
|
Power on backlight: 43mA Max |
|
Measurement: 2A Max (backlight off) |
quality |
Instrument: 2397g (including battery) |
|
Test line: 850g (including simple test line) |
|
Instrument box: 1200g |
Working temperature and humidity |
-10℃~40℃; Below 80% RH |
Storage temperature and humidity |
-20℃~60℃; Below 70% RH |
overload protection |
AC 280V/3 seconds between ports C1-C2 P1-P2 |
insulation resistance |
Above 10M Ω (500V between circuit and casing) |
Voltage resistance |
AC 3700V/rms (between circuit and casing) |
electromagnetic properties |
IEC61010-4-3, Wireless frequency electromagnetic field ≤ 1V/m |
Suitable for safety regulations |
IEC61010-1TheCATⅢ600VPollution level2TheJJG724-1991Verification Regulations for DC Digital OhmmetersJJG166-1993Verification Regulations for DC Resistors《DL/T967-2005Verification Regulations for Loop Resistance Testers and DC Resistance Rapid Testers |